Plan Review Notes
Plan Review Notes For Permit 09110225
Permit Number 09110225
Review Stop Z
Sequence Number 1
Notes
Date Text
2009-12-01 14:33:581. PLEASE SUBMIT FLOOR PLAN WITH EXISTING CONDITIONS
 AND DEMOLITION PLAN.
 2. PLEASE INDICATE THE PROPERTY LINE ON ALL FLOOR PLANS
 AND ELEVATIONS.
 3. FOLDINGS DOORS SHALL NOT ENCROACH INTO THE ROW.
 PLEASE VERIFY.
 4. PLEASE INDICATE DIMENSION OF NEW 2ND FLOOR BALCONY
 TO VERIFY COMPLIANCE. BALCONIES SHALL NOT BE LESS THAN
 4 FEET FROM THE BACK OF CURB.
 5. FOR THE FIRST FLOOR PLAN, PLEASE INDICATE EXISTING
 SIDEWALK CONDITIONS, MATERIALS, TREE GRATES AND TREES,
 AND LOCATE THE BACK OF CURB TO VERIFY COMPLIANCE WITH
 REQUIRED SETBACK.
 6. PLEASE SUBMIT LANDSCAPE DRAWINGS FOR ROOF TOP
 TERRACE. A MINIMUM OF 20% TREE CANOPY IS REQUIRED. SEE
 TABLE IV-8 ON SECTION 94-109 OF THE ZLDR.
 7. PLEASE STUDY THE POSIBILITY TO ENHANCE THE ALLEY
 FACADE WITH CERTAIN PERCENTAGE OF OPENINGS AND
 ARCHITECTURAL FEATURES.
 8. PLAES PROVIDE A DETAIL TABLE INDICATING THE TOTAL
 AREA OF THE SITE, AND THE AREA FOR THE BUILDING. PLEASE
 SEPARATE SQUARE FOOTAGE BASED OF DEFINITION FOR GROSS
 BUILIDNG AREA IN SECTION 94-109 OF THE ZLDR.
 9. PLEASE INDICATE TOTAL BUILDING HEIGHT AND BUILDING
 FOOTPRINT FOR EACH FLOOR.