2009-12-09 08:47:16 | |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| |
| 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| |
| 3. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE. |
| |
| 4. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE. |
| |
| 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. |
| |
| 6. EMPLOYEES SHALL BE TRAINED IN CROWD MANAGEMENT |
| PROCEDURES. PLEASE GO TO MARYLAND STATE FIRE MARSHAL'S |
| WEB SITE AND CLICK ON THE CROWD MANAGEMENT TRAINING |
| ICON. EMPLOYEES ARE TO WATCH THE TRAINING VIDEO AND |
| COMPLETE THE TEST. CERTIFICATES ARE TO BE PROVIDED TO |
| THIS OFFICE. |
| |
| 7. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL HANDRAILS AND GUARDRAILS. |
| |
| 8. EXIT DOORS ON SOME SHEETS ARE SWINGING IN THE WRONG |
| DIRECTION. |
| |
| 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, |
| DUCT, AND FIRE SUPPRESSION SYSTEMS. |
| |
| 10. INTERIOR FINISH MATERIALS SUCH AS THE THATCH ROOF |
| MATERIALS SHALL BE FIRE RETARDANT. |
| |
| 11. PLANS INDICATE INTERIOR FINISH FOR A MERCANTILE |
| OCCUPANCY. THE OCCUPANCY WILL BE AN ASSEBLY OCCUPANCY. |
| |
| 12. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A |
| MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE |
| NUMBERS ARE REQUIRED. |
| |
| 13. PLEASE INDICATE SLIP RESISTANT METHODS PLANNED FOR |
| THE EXTERIOR STAIRS. |
| |
| 14. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED. PLEASE |
| PROVIDE FIRE SPRINKLER DRAWINGS AND HYDRAULIC |
| CALCULATIONS. SEPARATE PLANS AND PERMITS REQUIRED. |
| |
| 15. NO FIRE ALARM SYSTEM INFORMATION PROVIDED. THE FIRE |
| ALARM SYSTEM SHALL BE A VOICE EVACUATION TYPE. SEPARATE |
| PLANS AND PERMITS REQUIRED. |
| |
| 16. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR |
| SCHEDULE INDICATING THE TYPE OF HARDWARE PLANNED. EXIT |
| DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR MORE |
| PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. FIRE |
| RATED DOORS SHALL BE EQUIPPED WITH LISTED FIRE RATED |
| EXIT HARDWARE. ALL RATED DOORS SHALL BE EQUIPPED WITH |
| SELF-CLOSING DEVICES. |
| |
| 17. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR ALL |
| STAIRS. |
| |
| 18. DOOR OPENINGS OBSERVED ON WEST ELEVATION NEAR EXIT |
| DOORS. |
| |
| 19. NO LIGHT FIXTURES OBSERVED FOR WEST EXIT STAIRS. |
| |
| 20. ALL COOLERS AND FREEZERS SHALL BE PROVIDED WITH |
| FIRE SPRINKLER PROTECTION. |
| |
| 21. PLEASE INDICATE SEATING LOCATIONS FOR PHYSICALLY |
| CHALLENGED PERSONS. |
| |
| 22. PLEASE PROVIDE FIRESTOPPING DETAILS. |
| |
| 23. PLEASE INDICATE HOURLY FIRE RATINGS OF EXISTING |
| STAIRS AND ALL VERTICAL SHAFTS WHETHER NEW OR EXISTING. |
| |
| 24. ONE OF THE EXIT STAIRS TERMINATES INTO KITCHEN 109. |
| PLEASE REVIEW EXITING THROUGH KITCHEN REQUIREMENTS. |
| |
| 25. ELEVATOR WARNING SIGNS ARE REQUIRED AT ELEVATOR |
| LOCATIONS. |
| |
| 26. WHO'S PROPERTY DOES THE REAR EXIT STAIR TERMINATES |
| ONTO. |
| |
| 27. EXISTING DOOR IS LOCATED WITHIN AN EXISTING STAIR. |
| WHAT IS THE PURPOSE OF THIS DOOR. SINCE NO EXITING |
| OCCURS THIS AREA NEEDS TO BE SEALED. |
| |
| 28. SOME BUILDING ELEMENTS AND FURNITURE APPEAR TO BE |
| LOCATED OVER THE PROPERTY LINE. AIR RIGHTS APPEAR TO BE |
| REQUIRED. |
| |
| 29. PLEASE ILLUSTRATE ANY NATURAL GAS SUPPLY LINES AND |
| APPURTENANT EQUIPMENT. |
| |
| DENIED. |
| |
| |