Plan Review Notes
Plan Review Notes For Permit 09110225
Permit Number 09110225
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-09 08:47:16 
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE.
  
 4. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 6. EMPLOYEES SHALL BE TRAINED IN CROWD MANAGEMENT
 PROCEDURES. PLEASE GO TO MARYLAND STATE FIRE MARSHAL'S
 WEB SITE AND CLICK ON THE CROWD MANAGEMENT TRAINING
 ICON. EMPLOYEES ARE TO WATCH THE TRAINING VIDEO AND
 COMPLETE THE TEST. CERTIFICATES ARE TO BE PROVIDED TO
 THIS OFFICE.
  
 7. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 8. EXIT DOORS ON SOME SHEETS ARE SWINGING IN THE WRONG
 DIRECTION.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 10. INTERIOR FINISH MATERIALS SUCH AS THE THATCH ROOF
 MATERIALS SHALL BE FIRE RETARDANT.
  
 11. PLANS INDICATE INTERIOR FINISH FOR A MERCANTILE
 OCCUPANCY. THE OCCUPANCY WILL BE AN ASSEBLY OCCUPANCY.
  
 12. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE
 NUMBERS ARE REQUIRED.
  
 13. PLEASE INDICATE SLIP RESISTANT METHODS PLANNED FOR
 THE EXTERIOR STAIRS.
  
 14. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED. PLEASE
 PROVIDE FIRE SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS. SEPARATE PLANS AND PERMITS REQUIRED.
  
 15. NO FIRE ALARM SYSTEM INFORMATION PROVIDED. THE FIRE
 ALARM SYSTEM SHALL BE A VOICE EVACUATION TYPE. SEPARATE
 PLANS AND PERMITS REQUIRED.
  
 16. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR
 SCHEDULE INDICATING THE TYPE OF HARDWARE PLANNED. EXIT
 DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. FIRE
 RATED DOORS SHALL BE EQUIPPED WITH LISTED FIRE RATED
 EXIT HARDWARE. ALL RATED DOORS SHALL BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
  
 17. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR ALL
 STAIRS.
  
 18. DOOR OPENINGS OBSERVED ON WEST ELEVATION NEAR EXIT
 DOORS.
  
 19. NO LIGHT FIXTURES OBSERVED FOR WEST EXIT STAIRS.
  
 20. ALL COOLERS AND FREEZERS SHALL BE PROVIDED WITH
 FIRE SPRINKLER PROTECTION.
  
 21. PLEASE INDICATE SEATING LOCATIONS FOR PHYSICALLY
 CHALLENGED PERSONS.
  
 22. PLEASE PROVIDE FIRESTOPPING DETAILS.
  
 23. PLEASE INDICATE HOURLY FIRE RATINGS OF EXISTING
 STAIRS AND ALL VERTICAL SHAFTS WHETHER NEW OR EXISTING.
  
 24. ONE OF THE EXIT STAIRS TERMINATES INTO KITCHEN 109.
 PLEASE REVIEW EXITING THROUGH KITCHEN REQUIREMENTS.
  
 25. ELEVATOR WARNING SIGNS ARE REQUIRED AT ELEVATOR
 LOCATIONS.
  
 26. WHO'S PROPERTY DOES THE REAR EXIT STAIR TERMINATES
 ONTO.
  
 27. EXISTING DOOR IS LOCATED WITHIN AN EXISTING STAIR.
 WHAT IS THE PURPOSE OF THIS DOOR. SINCE NO EXITING
 OCCURS THIS AREA NEEDS TO BE SEALED.
  
 28. SOME BUILDING ELEMENTS AND FURNITURE APPEAR TO BE
 LOCATED OVER THE PROPERTY LINE. AIR RIGHTS APPEAR TO BE
 REQUIRED.
  
 29. PLEASE ILLUSTRATE ANY NATURAL GAS SUPPLY LINES AND
 APPURTENANT EQUIPMENT.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
 MCARSILLO@WPB,ORG
2009-12-08 13:48:36SENT TO MIKE CARSILLO