2009-12-02 17:08:48BUILDING PLAN REVIEW
 PERMIT: 09110225
 ADD: 115 S OLIVE AVE
 CONT: TO BE DETERMINED/ CONTACT JOHN WEBB
 TEL: (561312-6247
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 DECEMBER 02/ 2009
 ACTION: DENIED
  
 1) A CONTRACTOR WITH THE CORRECT LICENSURE TO BE SIGNED
 ONTO THE PERMIT BEFORE ISSUANCE OF THE PERMIT FL S S
 489.
  
 2) BUILDING IS TO BE CONSIDERED A THRESHOLD BUILDING BY
 FL S S 553.71(7) AN ASSEMBLY BUILDING WHICH EXCEEDS
 5,000 SQUARE FT. AND AN OCCUPANT LOAD OF 500
 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) INFORMATIONAL, 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) SHEET A-2 FIRST FLOOR:
 4A) PLEASE REVIEW BUILDING TYPE OF CONSTRUCTION, PLANS
 INDICATE A TYPE V STRUCTURE TABLE 503 FOR A A2
 OCCUPANCY PLEASE DECLARE A "A OR B", NOTE 504.2 THE
 AUTOMATIC SPRINKLER INCREASE WILL ONLY PROVIDE A STORY
 INCREASE, THE MINIMUM COULD BE EITHER A VA (PROTECTED
 OR A IIIB UNPROTECTED).
  
 4B) THE PLANS ARE NOT CLEAR TO WHERE THE FRONT PROPERTY
 LINE IS LOCATED, IT APPEARS THE BAR STOOLS AND FOLDING
 DOORS MAY BE PAST THE PROPERTY LINE, PLEASE INDICATE
 THE LOCATION OF THE FRONT PROPERTY LINE. 3202.2 DOORS
 AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC
 RIGHT -OF-WAY.
  
 4C) THE BACK STAIRWAY APPEARS TO BE DUMPING TO THE
 INTERIOR OF THE BUILDING NOT WITHIN A VESTIBULE BUT
 INTO THE KITCHEN AREA PLEASE REVIEW EGRESS THROUGH
 KITCHENS, SECTION 1014.2(2).
  
 4D) THE FIRST FLOORA-2 ASSEMBLY AREA WITH THE CURRENT
 LAYOUT ONLY HAS ONE MEANS OF EGRESS, THROUGH THE FRONT
 ENTRY, NOTE TABLE 1019.2 BUILDING WITH ONE EXIT FOR AN
 ???A??? ASSEMBLY 49 OCCUPANT LOAD AND TRAVEL DISTANCE
 OF 75 FEET.
  
 4E) BAR SEATING 102 DOES NOT INDICATE IF THIS IS NEW
 CONSTRUCTION OR IF PART OF THE ALTERATIONS PLEASE
 REVIEW 11-5.4 & EXCEPTIONS TO PROVIDE VERTICAL
 ACCESSIBILITY.
  
 4F) THIS COMMENT WILL STAND FOR ALL THREE FLOOR LEVELS
 PLANS INDICATE A MERCANTILE OCCUPANCY FOR THE MINIMUM
 FLAME SPREAD AND SMOKE DEVELOPMENT, PLEASE UPDATE FOR
 AN A2 OCCUPANCY, TABLE 803.5. THE PLANS ARE DEFICIENT
 IN THE WALL & CEILING FINISHES. SHEET A1 DOES PROVIDE
 THE PARAMETERS FOR THE MATERIALS FOR FLAME SPREAD &
 SMOKE DEVELOPMENT BUT NOT THE ACTUAL FINISH MATERIALS.
 OUR CONCERNS ARE:
  
 4F)(1) 803.4.1 DIRECT ATTACHMENT AND FURRED
 CONSTRUCTION.
  
 4F)(2) 803.4.2 SET-OUT CONSTRUCTION.
  
 4F)(3) 803.4.4 MATERIALS.
  
 4F)(4)803.6 TEXTILES.
  
 4G)(5) 803.9.1 MATERIALS AND INSTALLATION. ACOUSTICAL
 MATERIALS COMPLYING WITH THE INTERIOR FINISH
 REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND
 APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH.
  
 4G)(6) 806.3 FOAM PLASTIC. FOAM PLASTIC USED AS TRIM IN
 ANY OCCUPANCY SHALL COMPLY WITH SECTION 2604.2.
  
 4G)(7)806.4 PYROXYLIN PLASTIC. IMITATION LEATHER OR
 OTHER MATERIAL CONSISTING OF OR COATED WITH A PYROXYLIN
 OR SIMILARLY HAZARDOUS BASE SHALL NOT BE USED IN GROUP
 A OCCUPANCIES.
  
 4G)(8) 806.5 INTERIOR TRIM. MATERIAL, OTHER THAN FOAM
 PLASTIC USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD AND SMOKE-DEVELOPED INDEX WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84, AS DESCRIBED IN
 SECTION 803.1. COMBUSTIBLE TRIM, EXCLUDING HANDRAILS
 AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT OF THE
 AGGREGATE WALL OR CEILING AREA IN WHICH IT IS LOCATED.
  
 4G)(9) PLANS INDICATE FALSE THATCHED ROOF BY OTHERS,
 PROVIDE INFO FOR 803.2/ 803.2.1.
  
 4H) PLANS INDICATE BATTERY BACK UP EMERGENCY BACK UP
 LIGHTS, BUT FAIL TO INCLUDE THE STAIRWELLS SECTION
 1006.2.
  
 4I) THIS COMMENT WILL STAND FOR ALL FLOORS , PLEASE
 INDICATE ON THE LIFE SAFETY PLAN THE ACCESSIBLE
 SEATING11-5.1 AND ACCESS AISLES 1014.3, 1014.3 (1)-(3).
  
 4J) PLANS FAIL TO INDICATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS, 906.1.
  
 4K) PLANS DO NOT INDICATE IF THE ELEVATOR AND
 DUMBWAITER ARE NEW OR EXISTING ELEMENTS, PLEASE PROVIDE
 WALL TAGS IDENTIFYING FIRE RATED WALLS (SHAFTS) SECTION
 707.4.AND RATED DOORS SECTION 715,.
  
 4L) PLANS DO NOT HAVE ANY DOOR SCHEDULE INDICATING THE
 SIZE OF THE DOOR, FIRE RATING NOR
 GLAZING WITHIN THE DOOR ETC, 715.3 OPENING
 PROTECTIVE???S, 11-4.13.5.
  
 5) SHEET A-3:
  
 5A) THE COMMON PATH OF TRAVEL HAS BEEN EXCEEDED FROM
 THE MOST REMOTE POINT WITHIN THE LADIES RESTROOM TO THE
 CLOSET VERTICAL EXIT. 1014.3.
  
 5B) DOOR# 209 DOES NOT HAVE THE MANEUVERING CLEARANCES
 ON THE LATCH SIDE OF THE DOOR. PLEASE REVIEW 11-4.13.6
 AND FIGURE 25(A).
  
 6)SHEET A4:
 6A) PLANS ARE MISSING ARCHITECTURAL DETAIL FOR THIS
 LEVEL THEY APPEAR TO BE CONCEPTUAL IN MANNER AT THIS
 POINT, ADDITIONAL INFORMATION REQUIRED.106.1.2.
  
 6B) WHAT TYPE OF FLOOR CEILING ASSEMBLY IS INSTALLED ON
 THIS BUILDING? PLEASE INDICATE THE FLOOR LOADING OF THE
 FLOOR CEILING ASSEMBLY TABLE1607.1.
  
 6C) CURRENTLY THE PLANS DO NOT PROVIDE ENOUGH DETAILS,
 BUT A CONCERN IS THE AMOUNT OF OPENNESS TO THE SOUTH
 SIDE OF THE ISLAND BAR VERSES THE PROPERTY LINE. TABLE
 602 WILL REQUIRE A FIRE RATING DEPENDING ON THE
 BUILDING TYPE, TABLE 704.8 ALLOWS 25% OPENINGS FOR
 PROTECTED OPENINGS ( SPRINKLERS), THE ISSUE WILL BE THE
 FOOTNOTE ???I??? UNLIMITED UNPROTECTED OPENINGS! THE
 PLANS ALSO INDICATE A PARAPET WALL ON THE SOUTH SIDE
 WITH THE HEIGHT UNKNOWN, BUT COULD BE USED AS PART OF
 THE WALL PER CENT AGE.
  
 6D) THE NORTH STAIRWELL ADDITION AND THE SOUTH RESTROOM
 AND BEER COOLER WILL ALSO NEED TO PROVIDE WALL TAGS TO
 IDENTIFY WALL TYPES IN REQUIRED RATED HOURS TABLE 602.
  
 6E) THERE IS NO ROOFING PLAN FOR THIS ADDITIONAL STORY,
 PLANS ARE CONCEPTUAL.
  
 7A) SHEET A-7 INDICATES A NEW BALCONY, THE BOTTOM BEING
 LOCATED APPROXIMATELY 12???-6?????? TO THE BOTTOM OF
 THE NEW BALCONY. PLEASE REVIEW 3202.3.2 FOR ALLOWABLE
 ENCROACHMENT.
 CONCEPTUAL IN NATURE.
  
 7B) SHEET A-7 ALSO NEEDS TO PROVIDE DETAIL FOR THE
 CANOPY/ EYEBROW ABOVE THE 2ND FLOOR.
 WIND INFO FOR CANOPY, DESIGN INFO, CONCEPTUAL IN
 NATURE.
  
 8A) SHEET A8 CONCEPTUAL IN NATURE, CONCERNS ARE THE
 EGRESS DOORS BENEATH THE EXTERIOR STAIR TO BE 1 HR
 RATED.
  
 8B) PROVIDE A STAIR DESIGN WITH LOADING TABLE 1607.1,
 HANDRAILS 1012/ GUARDRAIL 1013.
  
 8C) A CONCERN ABOUT THE EXTERIOR STAIR BEING A REQUIRED
 EXIT AND LOCATED WITHIN 10???-0??? OF THE PROPERTY
 LINE. SECTION 1024.3 THIS SECTION IDENTIFIES THE
 PROTECTION NEEDED FROM FIRE FROM ADJACENT BUILDINGS,
 AND OR FUTURE BUILDINGS. WHILE THIS BUILDING IS A
 SPRINKLERED BUILDING THIS PORTION (EXTERIOR STAIR) DOES
 NOT INDICATE IT TO BE SPRINKLERED. THE OTHER ISSUE
 IS IS THIS AN EXIT OR EXIT ACCESS, FOR A FULLY
 SPRINKLERED BUILDING THE TRAVEL DISTANCE IS 250??? FROM
 THE MOST REMOTE POINT ON THE ROOF TOP AND TRAVEL
 DISTANCE DOWN THE STAIRS IT APPEARS TO BE LESS THAN 250
 FEET PLEASE VERIFY TRAVEL DISTANCE AND CONSIDER THE
 SPRINKLERING OF THE STAIRS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. NO PRODUCT APPROVALS WERE SUBMITTED FOR
 REVIEW. THIS REVIEW WAS FOR A CONCEPTUAL CONCEPT SINCE
 MUCH OF THE REQUIRED INFORMATION WAS NOT AVAILABLE!
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved