Plan Review Notes For Permit 09110210
Permit Number 09110210
Review Stop P
Sequence Number 1
Notes
Date Text
2009-11-30 10:35:342007 FBC W/2009 REVISIONS
  
  
 DENIED BY PLUMBING
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS. FBC
 R4101.6.3
  
 2) PROVIDE A PIPING DIAGRAM WITH ALL PIPE SIZES
 SPECIFIED. FBC R4101.6
  
 3) SPECIFY THE WATER VELOCITY IN FEET PER SECOND FOR
 THE FOR THE SUCTION AND SUPPLY LINES. FBC R4101.6.3
  
 4) SPECIFY THE MAXIMUM FLOW RATE OF THE PUMP IN GALLONS
 PER MINUTE FOR THE TDH OF THE SYSTEM BEING INSTALLED.
 SUBMIT THE SPECIFICATIONS AND FLOW CHART FOR THE PUMP
 THAT WILL BE USED. FBC R4101.7
  
 5) THE PUMP CURVE CHART SUBMITTED HAS A 3/4 HP PUMP
 INDICATED ON IT AND THE PLANS SPECIFY A 2 HP PUMP.
 PLEASE CORRECT.
  
 6) THE POOL HEATER IS REQUIRED BY FBC R4101.14.2 TO
 HAVE A PERMANENT BY-PASS OR ANTI-SIPHON DEVICE. SHOW
 COMPLIANCE.
  
 7) THE PIPING DIAGRAM ON SHEET 2 SHOWS TWO MAIN DRAINS
 FOR THE POOL AND THE SPA. THE DRAWING ON SHEET 1 SHOWS
 CHANNEL DRAINS. PLEASE COORDINATE DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]