2009-12-22 13:27:222007 FBC W/2009 REVISIONS
 NEW RESIDENTIAL POOL
  
 DENIED BY BUILDING
  
 1) ITEMS 2,3 FROM THE FIRST REVIEW WERE NOT ADDRESSED.
  
 2) THE TURNOVER RATE SPECIFIED ON THE PLANS IS 2.2 HRS.
 FOR A 14,178 GALLON POOL. THIS WILL REQUIRE A FLOW RATE
 OF 107.4 GPM. THE PUMP SPECIFIED HAS A MAXIMUM FLOW
 RATE OF 102 GPM. PLEASE REVISE. FBC R 4101.20 ALLOWS UP
 TO 12 HOURS FOR TURNOVER. IN ORDER TO DETERMINE THE
 TURNOVER RATE YOU WILL NEED TO KNOW THE TDH.
  
 3) AT A FLOW RATE OF 102 GALLONS PER MINUTE THAT IS
 SPECIFIED ON THE PLANS, THE 2.5" BRANCH PIPING BETWEEN
 THE TWO MAIN DRAINS EXCEEDS THE 6 FT/SEC ALLOWED BY
 ANSI/APSP-7.
  