Plan Review Notes
Plan Review Notes For Permit 09110202
Permit Number 09110202
Review Stop M
Sequence Number 1
Notes
Date Text
2009-11-10 13:56:24PROVISO
 1) TEST AND BALANCE REPORT REQUIRED FOR FINAL
 INSPECTION
 2) PLEASE REFER TO SECTION 507.2.1.1 OPERATIONS . THE
 ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN
 INTERLOCK WITH THE COOKING APPLIANCES .
 3) PLEASE REFER TO SECTION 805.1 MAKEUP AIR . FOR
 MECHANICAL MAKEUP AIR SYSTEMS THE EXHAUST AND MAKEUP
 AIR SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED TO INSURE
 THAT MAKEUP AIR IS PROVIED WHENEVER THE EXHAUST SYSTEN
 IS IN OPERATION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732