Date |
Text |
2010-01-13 12:04:53 | PLANS REDLINED, | | | | | | ALL HORN, STROBE, PULL STATIONS ARE REQUIRED TO MEET | | FBC 11-4.28.1,.2 AND .3. MIN CD LEVELS FOR STORBES ARE | | 75 CD, MIN DB LEVELS AND HEIGHTS ARE TO BE REVISED ON | | PLANS BEFORE ROUGH ALONG WITH ANY OTHER CHANGES. |
|