2010-01-06 16:57:43** CALCULATIONS MAILED STANDARD MAIL 12/22. THESE WERE
 LOCATED IN OFFICE WITH NO DATE STAMP WHEN RECEIVED.
 LOCATED ON 1/4/10
  
 ** DENIED **
  
  
 1) NOTE: THE NEW SUBMITTED ENERGY PERFORMANCE
 CALCULATIONS ARE NOT COORDINATING WITH PLANS. A CALL
 WAS PLACED TO ENGINEERING FIRM TO GO OVER COMMENTS,
 FIXTURES ETC.
 THERE ARE FIXTURES WHICH ARE NOT ON THE INPUT DATA
 REPORT.
 TRACK LIGHTING IS REQUIRED TO BE FIGURED AT THE WATTAGE
 PER EACH FIXTURE TIMES THE NUMBER OF FIXTURES OR 30VA
 PER FT (WHICHEVER IS GREATER). PLEASE SEE 13-415.AB.5,
 AND APPENDIX B4.1.1
 ** SOME FIXTURES SUCH AS S TYPE NEED TO BE INCLUDED.
 ** THE W FIXTURES ARE NOT LISTED ON THE FIXTURE LEGEND
 AS ANY SPECIFIC WATTAGE OR FIXTURE. BASED ON
 CONVERSATION WITH ENGINEER PLANS CAN BE REDLINED BY
 THIS OFFICE FOR A MAXIMUM WATTAGE FIXTURE HOWEVER THAT
 WATTAGE NEEDS TO BE INCLUDED ON THE IDR.
 ** THE T FIXTURES WHICH DO NOT FALL UNDER EXEMPTIONS IN
 13-415.AB.5 NEED TO BE INCLUDED. ( T3).
 ** THERE ARE NO P1 FIXTURES LISTED.
 ** THERE ARE NO P2 FIXTURES LISTED.
 ** ANY S OR S2 FIXTURES WHICH ARE ON FOR GENERAL
 LIGHTING AND ALSO COME ON FOR BATTERY BACK ARE REQUIRED
 TO BE INCLUDED. ONLY FIXTURES WHICH DO COME ON FOR ANY
 GENERAL LIGHTING PURPOSE AND ONLY COME ON DURING POWER
 FAILURE ARE NOT INCLUDED.
 ** D FIXTURES?
 ** PLEASE REVISE METHOD OF CONTROLS. THE IDR SHOWS
 MANUAL ON/OFF WHEN PLANS INDICATE AUTOMATED LIGHTING
 CONTROLS. ( THIS WOULD BE REDLINED IF ONLY ITEM.
 ** PLEASE EXPLAIN THE 32-200W METAL HALIDES SHOWN ON
 THE IDR AND THE 4-250 METAL HALIDES SHOWN ON THE IDR.
 WHERE ARE THESE FIXTURES ON THE PLANS?
  
  
 PLEASE CALL TO GO OVER FOR ANY QUESTIONS. THE
 ALLOWANCES UNDER THE 2007 FBC W/ 2009 SUPPLEMENTS HAVE
 COMPLETELY CHANGED FROM PREVIOUS CODES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  