2010-03-23 16:18:30 | 2007 FBC W/2009 REVISIONS |
| NEW SFR |
| FLOOD ZONE A5 |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD FOR THE COMPONENTS AND CLADDING AS REQUIRED |
| BY DCA RULE 9B-72 AND CITY AMENDMENTS. |
| |
| 2) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED |
| AND DATED BY THE PREPARER. FBC 13-600 |
| |
| 3) THE ENERGY CALCULATIONS SPECIFY A 60 GALLON GAS |
| WATER HEATER AND THE PLANS SHOW AN 80 GALLON ONE. |
| PLEASE CORRECT. |
| |
| 4) SHOW ON THE SITE PLAN A-1 THAT THE SURFACE DRAINAGE |
| REQUIREMENTS OF FBC R401.3 WILL BE MET AND THAT THE |
| SURFACE WATER WILL BE DIRECTED TO APPROVED COLLECTIONS |
| POINTS AND NOT ONTO ADJACENT PROPERTIES. |
| |
| 5) PLEASE UPDATE THE REFERENCES ON A-1 TO ACI 530, ACI |
| 530.1, ACI 318 AND ACI 301 TO THE 2005 EDITIONS AS THE |
| STANDARDS SPECIFIED IN CHAPTER 43 OF THE 2007 FBC |
| RESIDENTIAL. |
| |
| 6) PLEASE UPDATE THE STAIR NOTES ON SHEET A-11 FROM |
| 2004 TO THE 2007 FBCR. REVISE NOTE #1 TO R311.5.3.1. |
| |
| 7) REVISE THE GUARDRAIL NOTE 1 ON A-11 FROM NOT LESS |
| THAN 42" TO NOT LESS THAN 34" WHEN MEASURED VERTICALLY |
| FROM THE TREAD NOSINGS PER FBC R312.1. |
| |
| 8) THE LIVE LOAD NOTES FOR THE GUARDRAILS AND HANDRAILS |
| IN THE CHART ON A-11 WERE NOT GIVEN. SEE TABLE R301.5 |
| |
| 9) ON A-10 THE DRAFT STOPPING NOTE CODE SECTION IS FROM |
| THE 2004 HVHZ. PLEASE REVISE TO THE 2007 FBC R602.1.2 |
| WHICH REQUIRES FIREBLOCKING AT THE TOP AND BOTTOM OF |
| STAIR RUNS. |
| |
| 10) SUBMIT THE SPECIFICATIONS AND LISTING FOR THE BBQ |
| AND HOOD LOCATED ON THE LANAI OR INDICATE THAT THEY |
| WILL BE APPLIED FOR UNDER A SEPARATE PERMIT. |
| |
| 11) SPECIFY CEILING MATERIAL THAT WILL BE INSTALLED IN |
| THE LANAI AND THE COVERED PORCH ABOVE IT. |
| |
| 12) SHOW COMPLIANCE WITH FBC R309.2 FOR GARAGE |
| SEPARATION. 5/8" TYPE X GYPSUM BOARD IS REQUIRED |
| BETWEEN GARAGES AND HABITABLE ROOMS ABOVE. |
| |
| 13) ON A-10 THE BUILDING CROSS SECTION SHOWS A CONCRETE |
| FLOOR AT THE COVERED PORCH ABOVE THE LANAI. SHEET S-2 |
| AND 1 ON SD3 SHOWS WOOD TRUSSES. PLEASE CLARIFY. |
| |
| 14) THE H-35 SINGLE HUNG WINDOWS SPECIFIED AT TWO OF |
| THE SECOND FLOOR BEDROOMS, DO NOT HAVE THE REQUIRED 5.7 |
| SQFT MINIMUM NET CLEAR OPENING REQUIRED BY FBC R310.1.1 |
| FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. (WINDOWS R-1 |
| THRU R-4 AND S-1) REVISE PLANS. |
| |
| 15) ON SHEETS S-1 THE FOUNDATION PLAN AND S-2 THE FLOOR |
| FRAMING PLAN THE COLUMN AT THE LANAI THAT SUPPORTS THE |
| BEAMS B111 AND B112 IS NOT SPECIFIED. PLEASE PROVIDE |
| DETAILS FOR THIS COLUMN. |
| |
| 16) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE THE |
| MINIMUM ELEVATION IS REQUIRED TO BE 7' 6" ABOVE BASE |
| FLOOD ELEVATION. CITY ORDINANCES. AN ELEVATION |
| CERTIFICATE WILL BE REQUIRED BEFORE FINAL INSPECTION. |
| |
| 17) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| STRUCTURAL MULLIONS AND FIXED WINDOWS AS REQUIRED BY |
| DCA RULE 9B-72. |
| |
| 18) THE FRONT DOOR IS SPECIFIED ON THE PLAN AS BEING |
| 3'-6" X 8'-0" WITH A SIDE-LITE. THE PRODUCT APPROVAL |
| THAT WAS SUBMITTED FOR THE FRENCH DOORS HAS A MAXIMUM |
| SINGLE DOOR WIDTH OF 3 FEET. PLEASE CORRECT. |
| |
| 19) SUBMIT TWO COPIES OF CURRENT (2007 FBC) FLORIDA |
| PRODUCT APPROVALS OR MIAMI-DADE NOAS FOR THE ANKMAR |
| OVERHEAD GARAGE DOOR. THE INFORMATION SUBMITTED IS NOT |
| ACCEPTABLE. |
| |
| 20) THE PRODUCT APPROVALS FOR THE PGT SH WINDOWS IS FOR |
| SMALL MISSILE IMPACT ONLY. THE WINDOWS ARE REQUIRED TO |
| BE APPROVED FOR LARGE MISSILE IMPACT PER FBC |
| R301.2.1.2. |
| |
| 21) SPECIFY THE ROOF TILE ATTACHMENT THAT WILL BE USED |
| FOR THE MONIER "S" TILE. THE METHOD SELECTED MUST BE |
| CAPABLE OF RESISTING THE OVERTURN MOMENT FOR A 140 MPH |
| EXPOSURE C LOCATION. |
| |
| NOTE: BEFORE A PERMIT TO CONSTRUCT CAN BE |
| ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE PLANS MUST BE |
| STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. 233-5025 |
| |
| PLEASE PROVIDE A WRITTEN RESPONSE TO THE COMMENTS |
| INDICATING HOW THEY HAVE BEEN ADDRESSED. |
| |