Plan Review Notes For Permit 09110129 |
Permit Number |
09110129 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-09 14:17:05 | *****DENIED***** | | | | | | 1. AS WAS DONE IN THE FIRE ALARM RISER DIAGRAM, | | INDICATE/CLOUD DEVICES WHICH WERE AMENDED FOR THIS | | TENANT SUITE BUILDOUT. | | | | 2. THE ADDRESS FOR THE AMENDED FIRE ALARM DEVICES (AS | | INDICATED IN THE FIRE ALARM RISER DIAGRAM) DOES NOT | | CORRELATE WITH THE DEVICES SHOWN IN THE FIRE ALARM PLAN | | LAYOUT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|