Notes |
Date |
Text |
2009-11-09 10:36:46 | *****DENIED***** | | | | | | 1. THE SYMBOL FOR DEVICES PS 1-1-1 AND PS 1-3-1 DO NOT | | CORRELATE AS INDICATED ON FA 0.1 AND FA 1.0 SHEETS | | | | 2. ON SHEET FA 0.1, CORRELATE FIRE ALARM DEVICE COUNT | | INDICATED IN THE FIRE ALARM RISER DIAGRAM WITH THAT | | INDICATED IN THE NOTIFICATION APPLIANCE CIRCUIT | | CALCULATIONS FOR NEW REMOTE POWER SUPPLY #1 . | | | | 3. ON SHEET FA 1.0 (JUST ABOVE THE FIRE ALARM LEGEND) | | THERE ARE THREE BROKEN RECTANGULAR BOXES FROM LEFT TO | | RIGHT "C", "B", "A" ; HOWEVER THE SHELL LAYOUT FOR THE | | TENANT SPACES FROM LEFT TO RIGHT ARE SHOWN AS "A", "C", | | "B" . PLEASE CLARIFY AS TO WHAT THESE REPRESENT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|