Plan Review Notes
Plan Review Notes For Permit 09110083
Permit Number 09110083
Review Stop P
Sequence Number 1
Notes
Date Text
2009-11-18 13:46:01DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT 2 FLOOR PLAN. SHOW THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAIN. TABLE 403.1.
  
 2. SHT 2 DETAIL FOR THE TOILET ROOM INDICATES THE W/C
 TO BE 2'0" OFF THE WALL. FIGURE 28 SHOWS THE W/C TO BE
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. ALSO
 THE CLEAR FLOOR SPACE FOR THE W/C SHALL REFLECT THE
 REQUIREMENTS FOR THE CLEAR FLOOR SPACE IN FIGURE 28,
 NOT 30X48 INCHES AS INDICATED.
  
 3. SHT 2 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 ___W/C:
 A. 11-4.16.5 FLUSH CONTROLS
  
 ___LAV:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 4. SHT 4 SANITARY RISER DIAGRAM. PER SECTIONS 905.3 &
 905.4 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN
 SHALL CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAIN LINE. - EVERY DRY VENT SHALL RISE VERTICALLY TO A
 MINIMUM OF 6 INCHES ABOVE THE FLOOD RIM LEVEL OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE VENT
 PAST THE TOILET ROOM DOES NOT MEET THESE CODE
 REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  