2009-11-18 13:46:01 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| |
| 1. SHT 2 FLOOR PLAN. SHOW THE LOCATION OF THE REQUIRED |
| DRINKING FOUNTAIN. TABLE 403.1. |
| |
| 2. SHT 2 DETAIL FOR THE TOILET ROOM INDICATES THE W/C |
| TO BE 2'0" OFF THE WALL. FIGURE 28 SHOWS THE W/C TO BE |
| 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. ALSO |
| THE CLEAR FLOOR SPACE FOR THE W/C SHALL REFLECT THE |
| REQUIREMENTS FOR THE CLEAR FLOOR SPACE IN FIGURE 28, |
| NOT 30X48 INCHES AS INDICATED. |
| |
| 3. SHT 2 SHOW COMPLIANCE WITH THE FOLLOWING: |
| |
| ___W/C: |
| A. 11-4.16.5 FLUSH CONTROLS |
| |
| ___LAV: |
| A. 11-4.19.2 CLEARANCE |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| |
| 4. SHT 4 SANITARY RISER DIAGRAM. PER SECTIONS 905.3 & |
| 905.4 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN |
| SHALL CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL |
| DRAIN LINE. - EVERY DRY VENT SHALL RISE VERTICALLY TO A |
| MINIMUM OF 6 INCHES ABOVE THE FLOOD RIM LEVEL OF THE |
| HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. THE VENT |
| PAST THE TOILET ROOM DOES NOT MEET THESE CODE |
| REQUIREMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |