2009-12-01 19:44:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A/C NOTE #12 CALLS FOR CONDENSATE TO DISCHARGE IN
 MOP SINK. CONDENSATE SHALL NOT DISCHARGE INTO SANITARY
 SEWER SYSTEM PER CITY ORDINANCE. CONDENSATE FROM THE
 COOLING COIL SHALL BE CONVEYED FROM THE DRAIN PAN
 OUTLET TO AN APPROVED PLACE OF DISPOSAL, SUCH AS
 OUTDOORS AT A WATER PERMEABLE LOCATION, MIN. 12" FROM
 BUILDING PER FBC-M 307.2.1. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE.
  
 2. SHOW SIZES OF RETURN AIR TRANSFER DUCTS ON PLAN TO
 DEMONSTRATE COMPLAINCE WITH FBC-M 601.4 FOR BALANCED
 RETURN AIR FLOW.
  