2009-11-30 16:02:12 | ** DENIED ** |
| |
| 1) NOTE: THE FOLLOWING CODES ARE REFLECTED ON COVER |
| SHEET WHICH ARE NOT CURRENT ADOPTED CODES BASED ON |
| PERMIT APPLICATION DATE. |
| 2005 NFPA-70 (NEC) |
| 2006 NFPA-72 |
| |
| SHOULD BE: |
| 2008 NFPA70 |
| 2002 NFPA-72 |
| |
| 2) NOTE: LIGHTING CONTROLS FOR AUTOMATED SHUT OFF IS |
| REQUIRED FOR NON-EXAM ROOMS. 13-415.AB.1.1,.1.2. |
| LOCATIONS SUCH AS FILE STORAGE, PHONE/SERVER ROOM, NEW |
| BATHROOM WOULD BE SUCH LOCATIONS. |
| |
| 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.AB.5 (13-415.B.2.2) |
| |
| 4) NOTE: PLEASE INDICATE NEW OR EXISTING GFI FOR |
| CONDENSING UNIT. 230.63, 210.8B2 |
| |
| 5) NOTE: PLEASE KNOW THAT A REVISED PANEL SCHEDULE WILL |
| BE REQUIRED FOR NEW CIRCUITS AND EXISTING. THESE ARE |
| REQUIRED TO BE SPECIFIC TOR ROOMS AND AREAS IN WHICH |
| THEY FEED. |
| 408.4. |
| |
| 6) NOTE: PLEASE SEE MINIMUM CLEARANCES FROM BATH/SHOWER |
| LOCATIONS. PLANS INDICATE AN ELECTRICAL WATER HEATER |
| RIGHT NEXT TO THE SHOWER. IS THIS ACCURATE? |
| PLEASE SEE 422.30,31 FOR REQUIRED DISCONNECT FOR |
| ELECTRIC WATER HEATER. PLANS INDICATE A RECEPTACLE FOR |
| CONNECTION WHICH IS NOT PERMITTED. |
| |
| 7) NOTE: IF BUILDING CONTAINS FIRE ALARM, PLEASE |
| INDICATE HORN, STROBES, AND LEVELS FOR ADA PER FBC |
| 11-4.28.1,.2 AND.3. |
| |
| |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |