Plan Review Notes
Plan Review Notes For Permit 09110083
Permit Number 09110083
Review Stop E
Sequence Number 1
Notes
Date Text
2009-11-30 16:02:12** DENIED **
  
 1) NOTE: THE FOLLOWING CODES ARE REFLECTED ON COVER
 SHEET WHICH ARE NOT CURRENT ADOPTED CODES BASED ON
 PERMIT APPLICATION DATE.
 2005 NFPA-70 (NEC)
 2006 NFPA-72
  
 SHOULD BE:
 2008 NFPA70
 2002 NFPA-72
  
 2) NOTE: LIGHTING CONTROLS FOR AUTOMATED SHUT OFF IS
 REQUIRED FOR NON-EXAM ROOMS. 13-415.AB.1.1,.1.2.
 LOCATIONS SUCH AS FILE STORAGE, PHONE/SERVER ROOM, NEW
 BATHROOM WOULD BE SUCH LOCATIONS.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5 (13-415.B.2.2)
  
 4) NOTE: PLEASE INDICATE NEW OR EXISTING GFI FOR
 CONDENSING UNIT. 230.63, 210.8B2
  
 5) NOTE: PLEASE KNOW THAT A REVISED PANEL SCHEDULE WILL
 BE REQUIRED FOR NEW CIRCUITS AND EXISTING. THESE ARE
 REQUIRED TO BE SPECIFIC TOR ROOMS AND AREAS IN WHICH
 THEY FEED.
 408.4.
  
 6) NOTE: PLEASE SEE MINIMUM CLEARANCES FROM BATH/SHOWER
 LOCATIONS. PLANS INDICATE AN ELECTRICAL WATER HEATER
 RIGHT NEXT TO THE SHOWER. IS THIS ACCURATE?
 PLEASE SEE 422.30,31 FOR REQUIRED DISCONNECT FOR
 ELECTRIC WATER HEATER. PLANS INDICATE A RECEPTACLE FOR
 CONNECTION WHICH IS NOT PERMITTED.
  
 7) NOTE: IF BUILDING CONTAINS FIRE ALARM, PLEASE
 INDICATE HORN, STROBES, AND LEVELS FOR ADA PER FBC
 11-4.28.1,.2 AND.3.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  