Plan Review Notes For Permit 09110048 |
Permit Number |
09110048 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-24 09:46:20 | SIGN, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- ENGINEERING DRAWINGS ARE MISSING THE FOLLOWING: | | A) ATTACHMENT OF BRACKET TO THE 4" ALUMINUM TUBE. | | B) ATTACHMENT OF 4" ALUMINUM TUBE TO THE SIGN BOX. | | C) COMPLETE INFORMATION FOR CONSTRUCTION OF SIGN. THERE | | IS NOT INFORMATION SUBMITTED. PROVIDE COMPLETE | | SPECIFICATIONS AND DETAILS FOR SIGN CONSTRUCTION TO | | SHOW COMPLIANCE WITH THE DESIGN PRESSURES OF SECTION | | 1609 FBC 2007. | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION TO | | INCLUDE ALL LABOR, MATERIALS AND ENGINEERING FEES. | | PROVIDE COPIES OF SIGNED CONTRACTS. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|