2009-11-06 10:53:43REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 SHOWS SUPPLY AND EXHAUST DUCTS PENETRATING
 1-HOUR RATED WALL. SEE WALL TYPE "B" AS SHOWN ON PAGE
 A3.0. SHOW HOW THESE PENETRATIONS ARE TO BE PROTECTED
 IN ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 2. THE FULL-HEIGHT FIRE RESISTANCE RATED WALL WILL
 PROHIBIT THE FLOW OF RETURN AIR THROUGH THE PLENUM
 CEILING BACK TO THE AIR HANDLING EQUIPMENT. PROVIDE
 TRANSFER AIR OPENINGS IN THE RATED WALL TO FACILITATE
 BALANCED RETURN IN ACCORDANCE WITH FBC-M 601.4. ALSO,
 SHOW HOW THESE TRANSFER OPENINGS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 3. PAGE M1 SHOWS CEILING EXHAUST FANS WITH POSITIVE
 PRESSURE EXHAUST DUCTS WITHIN THE PLENUM CEILING.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND
 INTO OR PASS THROUGH PLENUMS IN ACCORDANCE WITH FBC-M
 601.5.
  