Plan Review Notes For Permit 09100528 |
Permit Number |
09100528 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-06 10:53:43 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PAGE M1 SHOWS SUPPLY AND EXHAUST DUCTS PENETRATING | | 1-HOUR RATED WALL. SEE WALL TYPE "B" AS SHOWN ON PAGE | | A3.0. SHOW HOW THESE PENETRATIONS ARE TO BE PROTECTED | | IN ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | 2. THE FULL-HEIGHT FIRE RESISTANCE RATED WALL WILL | | PROHIBIT THE FLOW OF RETURN AIR THROUGH THE PLENUM | | CEILING BACK TO THE AIR HANDLING EQUIPMENT. PROVIDE | | TRANSFER AIR OPENINGS IN THE RATED WALL TO FACILITATE | | BALANCED RETURN IN ACCORDANCE WITH FBC-M 601.4. ALSO, | | SHOW HOW THESE TRANSFER OPENINGS ARE TO BE PROTECTED IN | | ACCORDANCE WITH FBC-M 607.5 AND 607.8. | | | | 3. PAGE M1 SHOWS CEILING EXHAUST FANS WITH POSITIVE | | PRESSURE EXHAUST DUCTS WITHIN THE PLENUM CEILING. | | EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND | | INTO OR PASS THROUGH PLENUMS IN ACCORDANCE WITH FBC-M | | 601.5. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|