Plan Review Notes For Permit 09100528 |
Permit Number |
09100528 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-19 09:51:35 | *****DENIED***** | | | | | | 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | REFERENCED, NOT THE 2003 EDITION AS STATED ON A1.0 | | SHEET. | | | | 2. THE PERMIT APPLICATION INDICATES THAT THE SCOPE OF | | WORK IS FOR SUITE 105, HOWEVER THE FOOR PLAN (SHEET | | A3.0) APPEARS TO INDICATE TWO SEPARATE TENAT SPACES. | | PLEASE EXPLAIN. | | | | 3. IN COMPARING SHEETS A3.0, A4.0, AND E2, IT APPEARS | | THAT DOOR #18 FROM OPEN AREA (105) EXITS TO ANOTHER | | TENANT SPACE IN THE BUILDING. PLEASE EXPLAIN. | | | | 4. IT IS STATED ON SHEET A1.0 THA THE BUILDING DOES NOT | | CONTAIN A FIRE ALARM SYSTEM. BASED UPON PREVIOUS FIELD | | INSPECTIONS CONDUCTED BY WEST PALM BEACH FIRE | | PREVENTION BUREAU, THIS BUILDING DOES HAVE A FIRE ALARM | | SYSTEM. PLEASE VERIFY AND IF THERE IS INDEED A FIRE | | ALARM SYSTEM IN THE BUILDING, PLEASE SHOW THE FIRE | | ALARM DEVICES IN THE SCOPE OF WORK LOCATION. | | | | 5. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL | | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|