2009-11-17 12:05:402007 FBC W/2009 REVISIONS
 STORM PANELS
  
 DENIED
  
 1) DIRECT MOUNT IS SPECIFIED FOR SOME OF THE STORM
 PANEL CONNECTION TYPES AND THE ONLY ANCHORS THAT ARE
 SPECIFIED ARE TAPCONS. TAPCONS ARE NOT ACCEPTABLE FOR
 DIRECT MOUNT PER PRODUCT APPROVAL.
  
 2) TABLE 2 NOTE ON PAGE 6 OF THE PRODUCT APPROVAL
 SPECIFIES A MINIMUM PANEL LENGTH FOR THE VARIOUS
 MOUNTING CONDITIONS. THE TABLE STATES THAT PANEL
 LENGTHS LESS THAN THOSE NOTED IN THE TABLE REQUIRE SITE
 SPECIFIC POROSITY CALCULATIONS BY A PROFESSIONAL
 ENGINEER. SOME OF THE PANEL LENGTHS ARE LESS THAN THE
 MINIMUMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW