Plan Review Notes
Plan Review Notes For Permit 09100489
Permit Number 09100489
Review Stop B
Sequence Number 1
Notes
Date Text
2009-11-02 12:30:432007 FBC W/2009 REVISIONS
 STORM PANELS
  
 DENIED BY BUILDING
  
 1) THE COMPONENT AND CLADDING PRESSURES FOR THE
 OPENINGS TO BE SHUTTERED ARE TOO LOW. PLEASE REVISE.
 FBC R301.2(2)
  
 2) THE ANCHOR SPACING FOR OPENING NUMBERS 5, 8 AND 11
 ARE INCORRECT FOR CORRECTED PRESSURES.
  
 3) THE ANCHOR TYPE ON THE SCHEDULE FOR THE ALUMINUM
 STORM PANELS IS SPECIFIED AS TAP CONS, HOWEVER ON THE
 PRODUCT APPROVAL THE ELCO PANEL MATES ARE SELECTED.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]