2009-11-02 10:51:131. THE NEW FIRE ALARM SYSTEM AND FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 2. SMOKE DETECTORS SHALL BE A MINIMUM OF AT LEAST THREE
 FEET FROM AIR CONDITIONER DIFFUSERS.
  
 3. TAMPER SWITCHES AND A CHAIN AND LOCK ARE REQUIRED ON
 THE FIRE LINE BACKFLOW DEVICE.
  
 4. ENTIRE INSTALLATION TO COMPLY WITH NFPA 72, THE
 NATIONAL FIRE ALARM CODE.
  
 5. EQUIPMENT IN AREAS THAT ARE SUBJECT TO DAMAGE SHALL
 BE PROPERLY PROTECTED FROM MECHANICAL DAMAGE. EXAMPLES
 INCLUDE THE GYMNASIUM THAT CAN BE DAMAGED BY
 BASKETBALLS.
  
 6. ON PAGE FA-2 2B DUCT DETECTORS SHALL CAUSE AN ALARM
 AND NOT A SUPERVISORY SIGNAL.
  
 7. PLEASE INDICATE IN WRITING WHAT THE VOICE EVACUATION
 MESSAGE WILL SAY. THIS MESSAGE WILL PROVIDE THE
 EMERGENCY INSTRUCTIONS THAT WILL BE PROVIDED BY THE
 FIRE ALARM CONTROL PANEL.
  