Plan Review Notes For Permit 09100423 |
Permit Number |
09100423 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-02 10:51:13 | 1. THE NEW FIRE ALARM SYSTEM AND FIRE SPRINKLER SYSTEM | | SHALL BE MONITORED BY A UL LISTED CENTRAL STATION | | APPROVED FOR CENTRAL STATION SERVICE. | | | | 2. SMOKE DETECTORS SHALL BE A MINIMUM OF AT LEAST THREE | | FEET FROM AIR CONDITIONER DIFFUSERS. | | | | 3. TAMPER SWITCHES AND A CHAIN AND LOCK ARE REQUIRED ON | | THE FIRE LINE BACKFLOW DEVICE. | | | | 4. ENTIRE INSTALLATION TO COMPLY WITH NFPA 72, THE | | NATIONAL FIRE ALARM CODE. | | | | 5. EQUIPMENT IN AREAS THAT ARE SUBJECT TO DAMAGE SHALL | | BE PROPERLY PROTECTED FROM MECHANICAL DAMAGE. EXAMPLES | | INCLUDE THE GYMNASIUM THAT CAN BE DAMAGED BY | | BASKETBALLS. | | | | 6. ON PAGE FA-2 2B DUCT DETECTORS SHALL CAUSE AN ALARM | | AND NOT A SUPERVISORY SIGNAL. | | | | 7. PLEASE INDICATE IN WRITING WHAT THE VOICE EVACUATION | | MESSAGE WILL SAY. THIS MESSAGE WILL PROVIDE THE | | EMERGENCY INSTRUCTIONS THAT WILL BE PROVIDED BY THE | | FIRE ALARM CONTROL PANEL. | | | | APPROVED PROVISO; | | | | MIKE CARSILLO, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | BUREAU OF FIRE PREVENTION | | 500 NORTH DIXIE HIGHWAY | | WEST PALM BEACH, FLORIDA 33401 | | (561) 804-4709 PHONE | | (561) 804-4774 FAX | | MCARSILLO@WPB,ORG | | WEST PALM BEACH |
|