Plan Review Notes For Permit 09100374 |
Permit Number |
09100374 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-21 11:30:48 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- A) PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED | | BY DCA RULE 9B-72 FOR FLAT ROOF. NONE WAS PROVIDED. | | | | B) SPECIFY ON FLAT ROOF PRODUCT APPROVAL WHICH APPROVED | | ASSEMBLY AND BASE SHEET FASTENING OPTION IS GOING TO BE | | INSTALLED. | | | | C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. | | ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED | | AND SEALED RAS 117 CALCULATIONS, THEN THEY NEED TO BE | | SIGNED AND SEALED. | | | | D) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO HAVE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE, THIS | | PROPERTY IS LOCATED ON EXPOSURE "C". | | | | 2- ACCORDING TO THE MIAMI-DADE COUNTY PRODUCT APPROVAL | | DIVISION, THE FILE FOR NOA 08-0204.07 WAS CLOSED. NEED | | TO PROVIDE CURRENT NOA. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|