Plan Review Notes
Plan Review Notes For Permit 09100327
Permit Number 09100327
Review Stop M
Sequence Number 3
Notes
Date Text
2009-12-15 08:22:21REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. *NOT ADDRESSED* SUPPLY FAN INTAKE LOUVER IS DIRECTLY
 ADJACENT TO AN ALLEY. MECHANICAL OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FEET
 HORIZONTALLY FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
 SOURCE, SUCH AS STREETS, ALLEYS AND PARKING LOTS IN
 ACCORDANCE WITH FBC-M 401.4.1 AND FBC-M 508.1.
  
 5. *NOT ADDRESSED* PROVIDE MANUFACTURER'S DATA SHOWING
 EF-1 IS DESIGNED FOR WIND RESISTANCE IN ACCORDANCE WITH
 FBC-M 301.12. IF MANUFACTURER'S DATA INCLUDES WIND
 RESISTANT INSTALLATION INSTRUCTIONS, ADJUST
 INSTALLATION DETAILS ON PLANS TO CORRESPOND WITH THOSE
 OF THE MANUFACTURER IN ACCORDANCE WITH FBC-M 304.1.
  
 6. *NOT ADDRESSED, ALSO NEED SUPPORT ON HORIZONTAL DUCT
 SECTION* OUTDOOR EXHAUST DUCT SHALL BE SECURED TO
 BUILDING STRUCTURE FOR WIND RESISTANCE PER FBC-M
 301.12. NO INFORMATION IS PROVIDED REGARDING
 CONSTRUCTION OF THE ANGLE SUPPORTS OR HOW THE DUCT IS
 TO BE ATTACHED TO THE SUPPORTS. GREASE DUCT BRACING AND
 SUPPORTS SHALL BE OF NONCOMBUSTIBLE MATERIAL SECURELY
 ATTACHED TO THE STRUCTURE AND DESIGNED TO CARRY GRAVITY
 AND WIND LOADS WITHIN THE STRESS LIMITATIONS OF THE
 FLORIDA BUILDING CODE, BUILDING IN ACCORDANCE WITH
 FBC-M 506.3.3. BOLTS, SCREWS, RIVETS AND OTHER
 MECHANICAL FASTENERS SHALL NOT PENETRATE DUCT WALLS.
 PROVIDE ALL MISSING INFORMATION AS REQUIRED PER THESE
 SECTIONS.
  
 7. OK
  
 8. OK
  
 9. *NOT ADDRESSED* PLANS SHOW A HEAT SENSOR INSTALLED
 AT THE EXHAUST INLET OF THE 14X16 DUCT AT THE LARGER
 HOOD TO FACILITATE AUTOMATIC OPERATION OF THE EXHAUST
 SYSTEM. HOWEVER, NO SUCH DEVICE IS SHOWN AT THE INLET
 OF THE 9X9 DUCT AT THE SMALLER HOOD. BOTH TYPE I HOOD
 SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER COOKING
 OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M 507.2.1.1.
  
 10. *NOT ADDRESSED* SUPPLY FAN AND EXHUST FAN ARE BOTH
 MARKED AS EF-1. LABEL FANS CORRECTLY ON PLANS IN
 ACCORDANCE WITH FBC-M 304.11.
  
 11. OK
  
 12. *NOT ADDRESSED* PROVIDE PRODUCT APPROVAL FOR
 PROPOSED LOUVER IN ACCORDANCE WITH FBC-M 106.3.3 AND
 FAC RULE 9B-72.
  
 13. *NOT ADDRESSED* THE STATED VALUE ON THE PERMIT
 APPLICATION IS LOW. THE CONTRACT WHICH WAS INCLUDED IN
 THE SUBMITTAL SHOWS A VALUE OF $32,000. THE VALUE AS
 STATED ON THE PERMIT APPLICATION HAS BEEN ADJUSTED TO
 REFLECT THE VALUE STATED ON THE CONTRACT. PAY
 OUTSTANDING FEE BALANCE OF $484.80 ASSOCIATED WITH THIS
 ADJUSTED VALUATION AT TIME OF RESUBMISSION. FBC-B
 108.3.
  
 14. *NOT ADDRESSED* THE ADDRESS ON THE PERMIT
 APPLICATION IS STATED AS "401 NORTHWOOD RD" WHILE THE
 ADDRESS ON THE PLANS IS STATED AS "403 NORTHWOOD RD."
 PLEASE CORRECT THE ADDRESS ON THE PLANS TO CORRESPOND
 WITH THE ADDRESS ON THE PERMIT ALLPICATION.
  