Plan Review Notes For Permit 09100241 |
Permit Number |
09100241 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-19 07:24:35 | 2007 FBC W/2009 REVISIONS | | EXISTING BUILDING | | LEVEL 3 ALTERATION | | | | | | DENIED BY BUILDING | | | | 1) THIS PROJECT IS CLASSIFIED AS A LEVEL 3 ALTERATION | | BECAUSE THE WORK AREA EXCEEDS 50 PERCENT OF THE | | AGGREGATE AREA OF THE BUILDING. SEE FBC EXISTING | | BUILDING 405. | | | | 2) SHOW AND EXPLAIN HOW COMPLIANCE WITH FBC 11-5.2 | | WHICH REQUIRES A SECTION OF THE COUNTER/BAR TO BE 34" | | IN HEIGHT AND 60" IN LENGTH OR SERVICE SHALL BE | | AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA. | | ALSO SEE 11-4.32. | | | | 3) THE WHEELCHAIR LIFT SHOWN ON THE DRAWINGS IS NOT | | REQUIRED. ACCESS IS NOT REQUIRED TO THE BACK KITCHEN. | | IT IS CONSIDERED A WORK AREA, IS NOT OPEN TO THE PUBLIC | | AND HAS AN OCCUPANT LOAD OF NO MORE THAN 5 PERSONS. IT | | IS NOT PART OF THE PRIMARY FUNCTION AREA. FBC 11-4.1.6 | | (1) (F). | | | | 4) THE STAIR IN THE MEANS OF EGRESS WITH A CHANGE IN | | LEVEL OF NOT EXCEEDING 21 INCHES IS REQUIRED TO HAVE A | | MINIMUM TREAD DEPTH OF 13 INCHES AND THE PRESENCE AND | | LOCATION OF EACH STEP SHALL BE READILY APPARENT PER FBC | | 1003.5.1. | | | | 5) FBC 1009.10 REQUIRES THE STAIR TO HAVE HANDRAILS ON | | EACH SIDE THAT COMPLY WITH SECTION 1012 AND 11-4.9.4. | | | | NOTE: THERE ARE 2 OF THE SAME SHEETS A-5.2 IN EACH OF | | THE PLAN SETS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|