Plan Review Notes For Permit 09100223 |
Permit Number |
09100223 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-10-15 14:03:13 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW SECOND | | CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ENGINEER NEEDS TO REVISE THE RAS 117 CALCULATIONS. | | ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE | | 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED | | ON EXPOSURE "C", NOT "B". THIS WAS NOTED ON THE FIRST | | CHECKLIST. | | | | 2- ENGINEER LETTER SPECIFIES APPROVED ASSEMBLY ON SHEET | | #16 WITH OPTION #1 FOR BASE SHEET FASTENING OPTION WITH | | MAXIMUM DESIGN PRESSURES OF -52.5PSF. PRODUCT APPROVAL | | SUBMITTED SHOWS APPROVED ASSEMBLY ON SHEET #17 WITH | | OPTION #1 BASE SHEET FASTENING OPTION WITH MAXIMUM | | DESIGN PRESSURES OF -45PSF. APPROVED ASSEMBLY SPECIFIED | | ON ENGINEER'S LETTER NEED TO MATCH APPROVED ASSEMBLY | | PROVIDED IN THE NOA SUBMITTED. COORDINATE AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|