Plan Review Notes
Plan Review Notes For Permit 09100223
Permit Number 09100223
Review Stop B
Sequence Number 2
Notes
Date Text
2009-10-15 14:03:13RESIDENTIAL (R3) REROOF, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER NEEDS TO REVISE THE RAS 117 CALCULATIONS.
 ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE
 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED
 ON EXPOSURE "C", NOT "B". THIS WAS NOTED ON THE FIRST
 CHECKLIST.
  
 2- ENGINEER LETTER SPECIFIES APPROVED ASSEMBLY ON SHEET
 #16 WITH OPTION #1 FOR BASE SHEET FASTENING OPTION WITH
 MAXIMUM DESIGN PRESSURES OF -52.5PSF. PRODUCT APPROVAL
 SUBMITTED SHOWS APPROVED ASSEMBLY ON SHEET #17 WITH
 OPTION #1 BASE SHEET FASTENING OPTION WITH MAXIMUM
 DESIGN PRESSURES OF -45PSF. APPROVED ASSEMBLY SPECIFIED
 ON ENGINEER'S LETTER NEED TO MATCH APPROVED ASSEMBLY
 PROVIDED IN THE NOA SUBMITTED. COORDINATE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712