Plan Review Notes
Plan Review Notes For Permit 09100214
Permit Number 09100214
Review Stop M
Sequence Number 1
Notes
Date Text
2009-10-27 17:44:38REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MECHNAICAL PLAN SHOWS NEW RTU MOUNTED ON ROOF CURB.
 STRUCTURAL PLAN SHOWS RTU SEVERAL FEET ABOVE THE ROOF
 SURFACE ON A FIELD-FABRICATED STAND. WHICH IS CORRECT?
 PLEASE CORRELATE MECHANICAL AND STRUCTURAL PLANS. ALSO,
 STRUCTURAL DETAIL PROVIDES NO INFORMATION ON ATTACHMENT
 OF THE RTU TO THE STAND FOR WIND RESISTANCE. SHOW HOW
 RTU IS TO BE ATTACHED TO SUPPORT BEAMS IN ACCORDANCE
 WITH FBC-M 301.12.
  
 2. SHOW ANY ROOFTOP DUCTWORK ASSOCIATED WITH THIS
 INSTALLATION WITH DETAILS, INSULATION REQUIREMENTS
 DRY-IN DETAIL. FBC-B 106.1.1.
  
 3. PROVIDE MANUFACTURER'S DATA SHOWING RTU IS DESIGNED
 FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12.
  
 4. PROVIDE MOTORIZED VOLUME DAMPER WITH SHUTOFF DAMPER
 CONTROLS ON NEW RTU IN ACCORDANCE WITH FBC-B
 13-409.AB.3.3.
  
 5. RTU SHALL HAVE DUCT SMOKE DETECTOR ON SUPPLY AND
 RETURN DUCTS IN ACCORDANCE WITH FBC-M 606.2.2.
  
 6. IS A MOTORIZED DAMPER REQUIRED TO PREVENT THE SUPPLY
 AIR FROM EXISTING AHU-5 FROM BACK-FEEDING INTO THE RTU
 WHEN THE RTU IS NOT IN USE? PLEASE CLARIFY.
  