Plan Review Notes For Permit 09100214 |
Permit Number |
09100214 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-27 17:44:38 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. MECHNAICAL PLAN SHOWS NEW RTU MOUNTED ON ROOF CURB. | | STRUCTURAL PLAN SHOWS RTU SEVERAL FEET ABOVE THE ROOF | | SURFACE ON A FIELD-FABRICATED STAND. WHICH IS CORRECT? | | PLEASE CORRELATE MECHANICAL AND STRUCTURAL PLANS. ALSO, | | STRUCTURAL DETAIL PROVIDES NO INFORMATION ON ATTACHMENT | | OF THE RTU TO THE STAND FOR WIND RESISTANCE. SHOW HOW | | RTU IS TO BE ATTACHED TO SUPPORT BEAMS IN ACCORDANCE | | WITH FBC-M 301.12. | | | | 2. SHOW ANY ROOFTOP DUCTWORK ASSOCIATED WITH THIS | | INSTALLATION WITH DETAILS, INSULATION REQUIREMENTS | | DRY-IN DETAIL. FBC-B 106.1.1. | | | | 3. PROVIDE MANUFACTURER'S DATA SHOWING RTU IS DESIGNED | | FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. | | | | 4. PROVIDE MOTORIZED VOLUME DAMPER WITH SHUTOFF DAMPER | | CONTROLS ON NEW RTU IN ACCORDANCE WITH FBC-B | | 13-409.AB.3.3. | | | | 5. RTU SHALL HAVE DUCT SMOKE DETECTOR ON SUPPLY AND | | RETURN DUCTS IN ACCORDANCE WITH FBC-M 606.2.2. | | | | 6. IS A MOTORIZED DAMPER REQUIRED TO PREVENT THE SUPPLY | | AIR FROM EXISTING AHU-5 FROM BACK-FEEDING INTO THE RTU | | WHEN THE RTU IS NOT IN USE? PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|