Plan Review Notes For Permit 09100214 |
Permit Number |
09100214 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-15 07:50:40 | 2007 FBC W/2009 REVISIONS | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) SPECIFY THE SIZES OF THE TWO NEW DOORS. DOOR SIZE | | SHALL COMPLY WITH FBC 1008.1.1 AND 11-4.13.5. | | | | 2) SHOW COMPLIANCE WITH FBC 1008.1.2, WHICH REQUIRES | | THE DOORS TO SWING IN THE DIRECTION OF TRAVEL. THE TWO | | NEW DOORS SWING IN THE WRONG DIRECTION WHEN THE | | DIRECTION OF TRAVEL IS TOWARD THE NEAREST OF THE TWO | | REQUIRED STAIR EXIT ENCLOSURES. | | | | 3) THE EGRESS TRAVEL PATHS FROM THE AREA WERE THE NEW | | WALLS AND DOORS ARE ENCLOSING APPEAR TO BE INCORRECT | | BASED ON THE LOCATION OF EXIT LIGHTS AND DIRECTIONAL | | ARROWS ON SHEET A-3. THE PATHS INDICATED APPEAR TO | | DIRECT THE OCCUPANTS TO TRAVEL AWAY FROM THE STAIR EXIT | | ENCLOSURES AND THROUGH THE RECEPTION AREA. EGRESS | | THROUGH INTERVENING SPACES DOES NOT ALLOW EGRESS | | THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS. | | THE COMMON PATH OF TRAVEL LENGTH CAN NOT BE EXCEEDED. | | PLEASE REVISE SO THAT THE PATH OF TRAVEL FROM THE | | ENCLOSED AREA WILL BE FROM THE CENTER OF THE AREA | | TOWARD EACH OF THE EXIT STAIR ENCLOSURES. | | | | 4) SHOW THE LONGEST TRAVEL DISTANCE FROM AREA THAT IS | | BEING ENCLOSED TO THE NEAREST EXIT STAIR ENCLOSURE ON | | THE LIFE SAFETY PLAN ON A-3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|