Plan Review Notes For Permit 09100193 |
Permit Number |
09100193 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-11-16 10:19:47 | 2007 FBC W/2009 REVISIONS | | RESIDENTIAL POOL | | | | DENIED BY PLUMBING | | | | 1) THE WATER VELOCITY IN THE 1-1/2 " RETURN LINES | | SPECIFIED ON THE PLANS WILL EXCEED THE 10 FT PER SECOND | | ALLOWED BY FBC R4101.6.3 FOR THE 1-1/2 HP PUMP THAT IS | | SPECIFIED. THE SIMPLIFIED TDH IS SHOWN AS 43.9 ON THE | | WORKSHEET AND THE PUMP SPECIFIED HAS A 90 GPM OUTPUT AT | | 40 FT OF HEAD. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|