Plan Review Notes For Permit 09100193 |
Permit Number |
09100193 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-02 08:47:17 | 2007/FBCR W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) ON SHEET 2, REVISE THE PUMP SIZE TO 1-1/2 HP TO | | CORRESPOND WITH THE SIZE SPECIFIED ON SHEET 1. | | | | 2) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD CALCULATIONS | | (TDH) AND PUMP CURVE GRAPHS FOR THE 1-1/2 HP PUMP THAT | | WILL BE INSTALLED. CALCULATIONS MUST SHOW THAT THE FLOW | | RATE DOES NOT EXCEED 6 FT/SEC IN THE MAIN DRAIN BRANCH | | PIPING. FBC R4101.6.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|