2009-11-02 08:47:172007/FBCR W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) ON SHEET 2, REVISE THE PUMP SIZE TO 1-1/2 HP TO
 CORRESPOND WITH THE SIZE SPECIFIED ON SHEET 1.
  
 2) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD CALCULATIONS
 (TDH) AND PUMP CURVE GRAPHS FOR THE 1-1/2 HP PUMP THAT
 WILL BE INSTALLED. CALCULATIONS MUST SHOW THAT THE FLOW
 RATE DOES NOT EXCEED 6 FT/SEC IN THE MAIN DRAIN BRANCH
 PIPING. FBC R4101.6.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714