Notes |
Date |
Text |
2009-11-02 08:16:25 | 2007 FBCR AND 2008 NEC | | | | 1) REVISE THE PUMP SIZE ON THE ELECTRICAL DRAWING FROM | | 2 HP TO 1-1/2 HP TO CORRESPOND WITH THE PUMP SIZE | | SPECIFIED ON SHEET 1. | | | | 2) UPDATE THE ELECTRICAL CODE REFERENCES TO THE 2008 | | NEC WHICH CAME INTO EFFECT ON OCTOBER 1, 2009. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|