Plan Review Notes
Plan Review Notes For Permit 09100090
Permit Number 09100090
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-09 15:51:08** PROVISO **
  
 ** PLEASE REVISE THE FOLLOWING ITEMS
  
 1) NOTE: PLEASE COORDINATE THE RISER, PANELS AND
 CONDUCTORS FOR THE FOLLOWING.
 A) RISER INDICATES 3-#8 AND 1-#10 FROM PANEL H TO
 TRANSFORMER HOWEVER PANEL H SCHEDULE INDICATES ALL AS
 #12 AWG.
 B) THE RISER INDICATES THE PANEL H AS BEING A 100AMP
 MLO, HOWEVER PANEL H SCHEDULE DETAILS INDICATES THIS AS
 A 100AMP MAIN CIRCUIT BREAKER PANEL.
  
 ** EITHER OF THE ABOVE FOUR SCENARIOS ARE CODE
 COMPLIANT HOWEVER PLANS NEED TO COORDINATE. PLEASE KEEP
 IN MIND #8 AWG WILL NOT FIT INTO A 20AMP BREAKER
  
 2) NOTE: PLANS NEED TO INDICATE THE MINIMUM LEVELS FOR
 ADA COMPLIANCE FOR HORN AND STROBE DEVICES. FBC
 11-4.28.1,.2 AND.3.
  
 ** PLANS NOTED FOR 210.4B OF THE 2008 NEC.
 ** LOW VOLTAGE PERMITS FOR PHONE/DATA/CATV, FIRE ALARM
 AND ANY ACCESS CONTROL SYSTEMS ARE UNDER SEPARATE
 PERMITS.
 THESE PLANS MAY BE REFERENCED FOR LV SYSTEMS OTHER THAN
 FA AND ACCESS CONTROLS.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  