2009-10-13 14:37:45FAILED
  
 PLEASE RESPOND TO COMMENTS IN WRITING. REVISED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS.
  
 1) A SURVEY, LESS THAN ONE YEAR OLD, OF THE SITE IS
 REQUIRED.
  
 2) THE EXPANSION OF THE PATIO AREA IS REMOVING THE
 PARKING ADJACENT TO THE BUILDING. A SITE PLAN SHALL BE
 PROVIDED VERIFYING THAT THE SITE HAS SUFFICIENT PARKING
 AFTER THE PARKING REMOVAL.
  
 3) THE EXPANSION OF THE PATIO AREA APPEARS TO ENCROACH
 INTO THE DRIVE AISLES. A SITE PLAN SHALL BE PROVIDED
 VERIFYING THAT THERE IS NO REDUCTION IN THE DRIVE AISLE
 WIDTH.
  
 4) THE PERMIT APPEARS TO INCLUDE AN EXPANSION OF THE
 SEATING AREA ON THE PATIO. IF THE SEATING AREA IS BEING
 INCREASED, THEN APPLICANT SHALL PROVIDE A SITE PLAN TO
 SHOW THAT THE RESTAURANT HAS ENOUGH ADDITIONAL PARKING
 TO ACCOMMODATE THE EXPANDED SEATING AREA.
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE FENCE/RAIL.
  
 6) ARE THE PLANTER BOXES MOVABLE OR ARE THEY FIXED TO
 THE GROUND.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  