2009-10-21 16:25:06STANDBY GENERATOR AND ABOVEGROUND STORAGE TANK (AST)
  
 1. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD"
 INSULATED TANK (2085) AS DESCRIBED ON THE PLANS. SOME
 INFORMATION IS SHOWN ON PAGE A-04.
  
 2. PLEASE ILLUSTRATE THE LOCATION OF ANY OPENINGS NEAR
 THE GENERATOR EXHAUST PIPE.
  
 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE GENERATOR.
  
 4. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 5. ENTIRE INSTALLATION TO COMPLY WITH NFPA 30.
  
 6. THE GENERATOR INSTALLATION SHALL ALSO COMPLY WITH
 NFPA 37.
  
 7. SEVERAL REQUIREMENTS OF THE FLORIDA BUILDING CODE
 ARE NOT BEING MET WITH THE PROPOSED INSTALLATION.
 PLEASE SEE BUILDING REVIEWER NOTES.
  
 8. AN ELEVATION DRAWING IS NEEDED WHERE THE PROPOSED
 EQUIPMENT IS BEING SHOWN.
  
 9. BASED ON THE SIZE CAPACITY OF THE PROPOSED FUEL TANK
 A SEPARATE FIRE RATED ENCLOSURE APPEARS TO BE
 NECESSARY.
  
 10. PLEASE ILLUSTRATE ON THE PLANS THE LOCATION OF THE
 TWO HOUR WALLS THAT SEPARATE THE PARKING STRUCTURE FROM
 OTHER PORTIONS OF THE BUILDING.
  
  
 DENIED
  
  