2009-10-21 16:25:06 | STANDBY GENERATOR AND ABOVEGROUND STORAGE TANK (AST) |
| |
| 1. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD" |
| INSULATED TANK (2085) AS DESCRIBED ON THE PLANS. SOME |
| INFORMATION IS SHOWN ON PAGE A-04. |
| |
| 2. PLEASE ILLUSTRATE THE LOCATION OF ANY OPENINGS NEAR |
| THE GENERATOR EXHAUST PIPE. |
| |
| 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE GENERATOR. |
| |
| 4. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE |
| NATIONAL ELECTRICAL CODE. |
| |
| 5. ENTIRE INSTALLATION TO COMPLY WITH NFPA 30. |
| |
| 6. THE GENERATOR INSTALLATION SHALL ALSO COMPLY WITH |
| NFPA 37. |
| |
| 7. SEVERAL REQUIREMENTS OF THE FLORIDA BUILDING CODE |
| ARE NOT BEING MET WITH THE PROPOSED INSTALLATION. |
| PLEASE SEE BUILDING REVIEWER NOTES. |
| |
| 8. AN ELEVATION DRAWING IS NEEDED WHERE THE PROPOSED |
| EQUIPMENT IS BEING SHOWN. |
| |
| 9. BASED ON THE SIZE CAPACITY OF THE PROPOSED FUEL TANK |
| A SEPARATE FIRE RATED ENCLOSURE APPEARS TO BE |
| NECESSARY. |
| |
| 10. PLEASE ILLUSTRATE ON THE PLANS THE LOCATION OF THE |
| TWO HOUR WALLS THAT SEPARATE THE PARKING STRUCTURE FROM |
| OTHER PORTIONS OF THE BUILDING. |
| |
| |
| DENIED |
| |
| |