Plan Review Notes For Permit 09100025 |
Permit Number |
09100025 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-26 08:28:34 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | TRANSFER SWITCH.AND GENERATOR. | | | | 2} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE | | EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF | | ON-SITE OPTIONAL STANDBY POWER SOURCES. | | | | 3} THE ELECTRICAL NOTES ON SHEET EO.1 INDICATE 2005 | | NFPA-70 AS THE GOVERNING CODE, THE 2008 EDITION WAS | | ADOPTED 10/1/09, PLEASE CHANGE THE REFERENCE. | | | | 4} THE FEEDER SCHEDULE LABLED "FH" ON SHEET E5.1 | | INDICATES 3 #1/0 CONDUCTORS. FOUR CONDUCTORS (NEUTRAL | | INCLUDED) WOULD BE REQUIRED PER 250.24 (C). ALSO THE | | CONTROLLER WILL MOST LIKLUDE 120 VOLT CIRCUITS | | | | 5} THE GENERATOR IS LABELED "EMERGENCY" ON E5.1, PLEASE | | NOTE THAT THE SYSTEM IS A 702 SYSTEM, NOT EMERGENCY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|