Plan Review Notes
Plan Review Notes For Permit 09100025
Permit Number 09100025
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-26 08:28:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 TRANSFER SWITCH.AND GENERATOR.
  
 2} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES.
  
 3} THE ELECTRICAL NOTES ON SHEET EO.1 INDICATE 2005
 NFPA-70 AS THE GOVERNING CODE, THE 2008 EDITION WAS
 ADOPTED 10/1/09, PLEASE CHANGE THE REFERENCE.
  
 4} THE FEEDER SCHEDULE LABLED "FH" ON SHEET E5.1
 INDICATES 3 #1/0 CONDUCTORS. FOUR CONDUCTORS (NEUTRAL
 INCLUDED) WOULD BE REQUIRED PER 250.24 (C). ALSO THE
 CONTROLLER WILL MOST LIKLUDE 120 VOLT CIRCUITS
  
 5} THE GENERATOR IS LABELED "EMERGENCY" ON E5.1, PLEASE
 NOTE THAT THE SYSTEM IS A 702 SYSTEM, NOT EMERGENCY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  