2009-10-05 14:24:21 | BUILDING PLAN REVIEW |
| PERMIT: 09100025 |
| ADD: 444 W RAILROAD AV. |
| CONT: (PLAN REVIEW) PBM DEV |
| TEL: (561)715-1800 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| OCT 05-2009 |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| 1) THE PLANS INDICATE THE MOVING OF THE ACCESSIBLE |
| PARKING SPACES NEXT TO THE ENTRY AND CREATING |
| ACCESSIBLE SPACES FURTHER AWAY FROM THE ENTRY AND ALSO |
| CAUSING THE DISSABLED TO TRAVEL BEHIND THE OTHER PARKED |
| VEHICLES. |
| |
| 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES SERVING A |
| PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST |
| SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| TO AN ACCESSIBLE ENTRANCE. |
| |
| 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.1) GENERAL. |
| ALTERATIONS TO EXISTING BUILDINGS AND FACILITIES SHALL |
| COMPLY WITH THE FOLLOWING: |
| |
| (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES |
| OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR |
| USABILITY OF A BUILDING OR FACILITY BELOW THE |
| REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF |
| ALTERATION. |
| |
| (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE |
| ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE, |
| FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE |
| PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3, |
| MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. |
| |
| |
| 2) SHEET A-4 INDICATES THE INSTALATION OF A 5,000 GAL |
| DESIEL FUEL DOUBLE WALL TANK. THIS IS IN EXCESS OF |
| ALLOWABLE COMBUSTIBLE LIQUIDS FOR A CLASS LL COMBUSTILE |
| LIQUIDS, SEE TABLE 307.7(1) WHEN OVER 240 GAL FOOTNOTE |
| D & E. |
| |
| 415.6.2 FLAMMABLE AND COMBUSTIBLE LIQUIDS. THE STORAGE, |
| HANDLING, PROCESSING AND TRANSPORTING OF FLAMMABLE AND |
| COMBUSTIBLE LIQUIDS SHALL BE IN ACCORDANCE WITH THE |
| FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA FIRE |
| PREVENTION CODE. |
| |
| 415.6.2.1 MIXED OCCUPANCIES. WHERE THE STORAGE TANK |
| AREA IS LOCATED IN A BUILDING OF TWO OR MORE |
| OCCUPANCIES, AND THE QUANTITY OF LIQUID EXCEEDS THE |
| MAXIMUM ALLOWABLE QUANTITY FOR ONE CONTROL AREA, THE |
| USE SHALL BE COMPLETELY SEPARATED FROM ADJACENT FIRE |
| AREAS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| 508.3.3. PLEASE INDICATE COMPLIANCE WITH THIS SECTION. |
| |
| |
| 3) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS FOR |
| COMPLIANCE WITH: |
| 415.6.2.5 LEAKAGE CONTAINMENT. A LIQUID-TIGHT |
| CONTAINMENT AREA COMPATIBLE WITH THE STORED LIQUID |
| SHALL BE PROVIDED. THE METHOD OF SPILL CONTROL, |
| DRAINAGE CONTROL AND SECONDARY CONTAINMENT SHALL BE IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| |
| EXCEPTION: ROOMS WHERE ONLY DOUBLE-WALL STORAGE TANKS |
| CONFORMING TO SECTION 415.6.2.3 ARE USED TO STORE CLASS |
| I, II AND IIIA FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL |
| NOT BE REQUIRED TO HAVE A LEAKAGE CONTAINMENT AREA. |
| |
| 4) PLEASE PROVIDE ANCHORING REQUIREMENTS FOR SLIPPAGE |
| AND UPLIFT 1604.8.1. |
| |
| 5) 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION |
| RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF |
| WHETHER WIND LOADS GOVERN THE DESIGN OF THE |
| LATERAL-FORCE-RESISTING SYSTEM OF THE BUILDING: |
| |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (M/S). |
| |
| 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 3. WIND EXPOSURE. WHERE MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF |
| EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| NOTICE. |
| |
| OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| - 5:00 PM. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| SURVEY: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |