2009-10-14 14:16:01****ISSUED WITH PROVISO****
 ****REVISION REQUIRED BEFORE FIRST INSPECTION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. EITHER REVISE WIND DESIGN CRITERIA TO EXPOSURE C OR
 HAVE ENGINEER JUSTIFY DESIGN CRITERIA OF EXPOSURE B
 (CAN CONTACT ME VIA TELEPHONE OR EMAIL). THE PLANS
 STATE THAT THIS JOB WAS DESIGNED TO FBC2004; PLEASE
 NOTE THAT THE CODE HAS CHANGED EFFECTIVE MARCH 1, 2009.
 PLEASE NOTE ALSO THAT THE DEFINITIONS OF EXPOSURE B AND
 EXPOSURE C HAVE CHANGED, SEE FBC2007 AND SUPPLEMENTS.
 THE CODE AND SUPPLEMENTS ARE AVAILABLE ONLINE AT
 WWW.FLORIDABUILDING.ORG.
  
 SEE FBC R301.2.1.4.3, DEFAULT FOR FLORIDA IS EXPOSURE
 C. BASED ON AERIALS, THIS JOB IS LOCATED IN EXPOSURE C.
  