Plan Review Notes For Permit 09090649 |
Permit Number |
09090649 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-12-14 16:29:59 | ** REDLINED PLANS. | | | | | | | | 1) NOTE: PLANS INDICATE THE 2008 NEC, HOWEVER PERMIT | | APPLICATION WAS MADE BEFORE 10/31/09 WHICH PLACES | | PROJECT UNDER THE 2005 NEC. | | | | 2) NOTE: AS NOTED PREVIOUSLY, ANY 15/20AMP 120 | | RECEPTACLES WITHIN 6FT OF LAUNDRY SINK SHALL BE GFI/GFI | | PROTECTED. AN EXAMPLE IS THE DEDICATED CIRCUIT SUCH AS | | THE WASHING MACHINE. THIS WAS REVISED IN THE 2005 NEC. | | | | 3) NOTE: RISER NOW INDICATES A NEW MAIN DISCONNECT | | WHICH IS OK, HOWEVER NOW THE RISER IS MISSING THE | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN TO THE SUB MLO | | PANEL INSIDE. PLEASE SIZE PER 250.122. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|