Plan Review Notes
Plan Review Notes For Permit 09090649
Permit Number 09090649
Review Stop B
Sequence Number 2
Notes
Date Text
2009-12-15 13:16:25BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE ROOF
 VENTILATION AS REQUIRED BY SEC. R806.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE CALCULATIONS SHOWN ON SHEET
 A1. NEED TO INCLUDE THE OVERALL ROOF AREA NOT JUST THE
 A/C AREA. ALSO, SIZE OF GABLE VENTS TO PROVIDE THE
 REQUIRED VENTILATION. PROVIDE CALCULATIONS SHOWING THE
 ACTUAL CLEAR AREA OF THE SPECIFIED VENTS.
  