2009-10-02 07:56:45**DENIED **
  
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS/LIGHTING
 DENSITIES SUBMITTED. 13-415.AB.5, 13-415.B.1.
 SOME FIXTURES ON PLANS NEED IDENTIFICATION TO
 COORDINATE WITH CALCULATIONS AND FIXTURE LEGEND. ( SEE
 STAIR LIGHTS)
  
 2) NOTE: ELECTRICAL PANEL NOT PERMITTED IN STORAGE
 CLOSET. 110.26,240.24D
  
 3) NOTE: STORAGE TYPE WATER HEATERS SHALL BE FIGURED AT
 125% AS THESE ARE CONSIDERED CONTINUOUS LOADS. 422.13
 WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY COMMENT.
  
 4) NOTE: PLEASE ADJUST AND COORDINATE SOME CIRCUITS.
 SEE CIRCUITING ON PLANS FOR HPU AND WATER HEATER. WH
 SHOWN ON CIRCUITS 1,3 AND HPU ON 22,24. THIS SHOULD BE
 REVERED.
 ALSO WOULD HAVE BEEN REDLINED IF NOT FOR COMMENTS #1
 AND #2.
  
 ** PLANS ARE ALSO COMING BACK FOR BUILDING REVIEW
 COMMENTS.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II