Plan Review Notes For Permit 09090605 |
Permit Number |
09090605 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-03 10:57:35 | ** PROVISO/REDLINED ** | | | | | | 1) NOTE: SELECTIVE COORDINATION STUDY TO BE SUBMITTED | | FOR REVIEW BEFORE INSPECTION. | | PLEASE SEE NEC 700.27, 701.18, 240.12 | | ALSO NFPA-110 CHAPTER 6, 6.5.1 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | |
|