2009-10-27 19:36:13REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN INDICATES THAT VENTILATION AND COMBUSTION AIR
 FOR THE GENERATOR IS TO BE TRANSFERRED THROUGH A
 LOADING DOCK INTO THE GENERATOR ROOM. THIS
 CONFIGURATION IS NOT PERMITTED. VENTILATION AIR SHALL
 BE SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE OF THE
 BUILDING BY AN EXTERIOR WALL OPENING OR FROM A SOURCE
 OUTSIDE THE BUILDING BY A 2-HOUR FIRE RATED AIR
 TRANSFER SYSTEM IN ACCORDANCE WITH NFPA 110-02 SECTION
 7.7.3.
  
 2. THE VENTILATION SUPPLY IS SHOWN BEING BROUGH INTO
 THE GENERATOR ROOM THROUGH A NEW 6' X 4' WALL OPENING
 IN THE BUILDING. WITH THIS OPENING, HOW WILL THE
 REQUIRED FIRE RATING OF THE GENERATOR ROOM BE
 MAINTAINED? THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING IN ACCORDANCE WITH NFPA 110-02 SECTION 7.2.1.1.
 ALSO, FIRE DAMPERS OR OTHER SELF-CLOSING DEVICES SHALL
 NOT BE PERMITTED IN VENTILATION OPENINGS OR DUCTWORK
 FOR SUPPLY OR RETURN/DISCHARGE AIR TO EPS EQUIPMENT FOR
 LEVEL 1 EPSS IN ACCORDANCE WITH NFPA 110-02 SECTION
 7.7.2.3. SHOW HOW THE FIRE RATING OF THE ROOM IS TO BE
 MAINTAINED.
  