2009-10-22 07:28:04GENERATOR REPLACEMENT - DIESEL
  
 1. WRONG CODES LISTED ON PAGE AO.1. PLEASE CORRECT CODE
 REFERENCES.
  
 2. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 3. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR NEW HANDRAILS DESCRIBED ON PAGE A.1.1.
  
 4. THE REFERENCES ON PAGE M-1.0 RELATED TO MAKE-UP AIR
 FROM THE LOADING DOCK IS NOT VERY CLEAR. PLEASE PROVIDE
 ADDITIONAL DETAILS.
  
 5. ANY ASBESTOS REGULATED MATERIALS SHALL BE PROPERLY
 HANDLED, COLLECTED, AND DISPOSED OF IN ACCORDANCE WITH
 FEDERAL, STATE, AND LOCAL REQUIREMENTS.
  
 6. INSTALLATION TO COMPLY WITH NFPA 110 AND NFPA 37.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION