2009-10-11 09:54:45 | |
| |
| ** DENIED ** |
| |
| |
| 1) NOTE: PLANS SUBMITTED FOR PERMIT AFTER MARCH 1ST |
| 2009 AND DECEMBER 31ST, 2008 ARE UNDER THE FOLLOWING |
| CODES. THE LIFE SAFETY CODE ON PLANS STATE 2000 EDITION |
| WHICH IS ACTUALLY FROM TWO CYCLES AGO. PLEASE SEE FAC |
| 69A FOR ADOPTIONS OF NFPA EDITIONS. |
| FAC 69A-60.004, 69A-3.012 AS OF DECEMBER 31ST 2008 |
| ADOPTED THE 2006 NFPA-101, 2006 NFPA-1 AND THE 2007 |
| FLORIDA FIRE PREVENTION CODE. |
| PLEASE SEE FBC 2007 W/ 2009 SUPPLEMENTS, FAC 69A-3.012 |
| AS DECEMBER 8TH, 2006 THE ELECTRICAL CODE IS THE 2005 |
| EDITION. |
| PLEASE ADJUST PLANS TO THE FOLLOWING WHICH ARE |
| RELEVANT. |
| |
| 2007 FBC W/2009 REVISIONS. |
| 2005 NFPA-70 |
| 2005 NFPA-110 |
| 2006 NFPA-101 |
| |
| ** FOR INFORMATION ONLY 2008 NFPA-70 WAS ADOPTED ON |
| OCTOBER 1ST, 2009. |
| |
| 2) NOTE: SEE NFPA-110 7.7.2.1 AND 7.7.2.2. THE MAKE UP |
| AIR IS SHOWN FROM AN INSIDE LOADING DOCK WHICH IS |
| SUPPLIED THROUGH ANOTHER OPENING. PLANS ALSO INDICATE A |
| *SCREEN GATE/DOOR OPENING* AT THE SAME LOCATION WHERE |
| VENTILATION IS BEING BROUGHT INTO? |
| SEE MINIMUM CODES AND RATING OF AIR INTAKES. |
| THIS WILL BE PART OF MECHANICAL REVIEW FOR TECHNICAL |
| REVIEW COMMENTS AND IS GIVEN AS INFORMATION ONLY BY |
| THIS REVIEWER. THE REVIEW OF THE VENTILATION SYSTEM IS |
| NOT UNDER THIS ELECTRICAL REVIEW. |
| |
| 3) NOTE: PLANS INDICATE WHAT WOULD BE A NEW EXIT AND |
| STAIRS HOWEVER NO LIGHTING PLANS WERE SUBMITTED FOR |
| GENERAL ILLUMINATION OR FOR EGRESS ILLUMINATION. |
| PLEASE SEE FBC 1006.1, NFPA-101 7.8.1.3,7.9.1.1,7.9.2 |
| AND INDICATE. |
| |
| 4) NOTE: PLEASE SEE NFPA-110 7.3 FOR MINIMUM LIGHTING |
| REQUIRED IN NEW GENERATOR ROOM. |
| |
| 5) NOTE: PLANS MAKE NOTE TO 700.27 FOR SELECTIVE |
| COORDINATION HOWEVER NO COORDINATION STUDY AND |
| DOCUMENTS WERE SUBMITTED. IF THIS INFORMATION IS NOT |
| KNOWN BASED ON EQUIPMENT, BREAKERS ETC THIS CAN BE DONE |
| AS A PROVISO TO BE SUBMITTED AT A LATER DATE. |
| |
| 6) NOTE: PLEASE EXPLAIN WHAT TYPE OF GENERATOR IS BEING |
| REPLACED AND LOADS SERVED? THE PLANS ALL LEND TO A 700, |
| 701 SYSTEM HOWEVER BASED ON PANEL SCHEDULES THERE ARE |
| 700, 701 AND 702 ALL WIRED INTO THE SAME PANELS ALL FED |
| FROM THE SAME TRANSFER SWITCH. THIS IS NOT PERMITTED. |
| A/C EQUIPMENT, GENERAL PURPOSE RECEPTACLES, GENERAL |
| LIGHTING ETC ARE NOT 700 SYSTEMS AND MAY NOT BE WIRED |
| INTO LIFE SAFETY/EMERGENCY SYSTEMS. |
| PLEASE PROVIDE PLANS FOR LIFE SAFETY LIGHTING |
| CIRCUITS/LAYOUTS. IF ALL MINIMUM LIFE SAFETY REQUIRED |
| EGRESS LIGHTING IS BATTERY BACK UP THEN ALL LIGHTING |
| WOULD BE CONSIDERED AS AN 702 BACK UP AND NOT BE FED |
| FROM THE 700 ATS. |
| SEE NEC 700.9B, SEE HANDBOOK AS THERE ARE FIGURES WHICH |
| CLEARLY SHOW SYSTEM SEPARATIONS. |
| RISER INDICATES A 225AMP BREAKER TO RE-FEED EM-CONTROL |
| PANEL HOWEVER NO INFORMATION FOR WHAT THIS PANEL IS |
| FEEDING IS SHOWN. NO TRANSFER SWITCH IS SHOWN. WILL |
| THIS PANEL BE FED FROM THE GENERATOR ONLY WHEN UNDER |
| EMERGENCY POWER? |
| PLANS ALSO STATE EXISTING WIRING AND LOADS HAVE NOT |
| BEEN VERIFIED. SOME CODE REVIEW ITEMS CAN NOT BE |
| CONFIRMED IF PLANS STATE THESE MAY NOT BE THE LOADS AND |
| WIRING? |
| |
| 7) NOTE: PLEASE INDICATE THE GROUNDING FOR T-EM? |
| 250.20,250.30,250.66 ETC |
| |
| 8) NOTE: PLEASE SEE NFPA- 110 7.4, 7.5 FOR LOCATIONS, |
| ATTACHMENTS ETC. |
| |
| |
| ** AS THERE WILL BE SEVERAL CHANGES MADE TO RISER, |
| PLEASE CALL TO GO OVER ANY ITEMS BEFORE RESUBMITTING TO |
| ALLEVIATE DELAY OF PROJECT. |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |