Plan Review Notes
Plan Review Notes For Permit 09090594
Permit Number 09090594
Review Stop M
Sequence Number 1
Notes
Date Text
2009-10-26 20:55:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MEDIUM CONFERENCE ROOM 1678 IS SHOWN WITH FULL
 HEIGHT PARTITIONS. THE LOCATION OF THESE PARTITIONS
 WOULD ISOLATE THE SMOKE CONTROL DUCT COMING FROM THE
 ADJACENT SHAFT INTO THE TENANT SPACE. THIS SMOKE
 CONTROL DUCT SERVES THE ENTIRE FLOOR AND CANNOT BE
 ISOLATED FROM THE REST OF THE FLOOR BY THESE
 PARTITIONS. SHOW HOW THIS INTERIOR DESIGN WILL NOT
 IMACT THE EXISTING SMOKE CONTROL SYSTEM.
  
 2. FLOOR PLAN SHOWS 18X12 SUPPLY DUCT PENETRATING WALL
 BETWEEN GALLERY 1687 AND LOBBY 1601. SEE BUILDING PLAN
 REVIEW COMMNETS REGARDING TENANT SEPARATION
 REQUIREMENTS. SHOW PROTECTION OF THE DUCT PENETRATION
 AT THIS LOCATION IN ACCORDANCE WITH FBC-M 607.5 AND
 FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: