2009-10-26 20:55:41 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. MEDIUM CONFERENCE ROOM 1678 IS SHOWN WITH FULL | | HEIGHT PARTITIONS. THE LOCATION OF THESE PARTITIONS | | WOULD ISOLATE THE SMOKE CONTROL DUCT COMING FROM THE | | ADJACENT SHAFT INTO THE TENANT SPACE. THIS SMOKE | | CONTROL DUCT SERVES THE ENTIRE FLOOR AND CANNOT BE | | ISOLATED FROM THE REST OF THE FLOOR BY THESE | | PARTITIONS. SHOW HOW THIS INTERIOR DESIGN WILL NOT | | IMACT THE EXISTING SMOKE CONTROL SYSTEM. | | | | 2. FLOOR PLAN SHOWS 18X12 SUPPLY DUCT PENETRATING WALL | | BETWEEN GALLERY 1687 AND LOBBY 1601. SEE BUILDING PLAN | | REVIEW COMMNETS REGARDING TENANT SEPARATION | | REQUIREMENTS. SHOW PROTECTION OF THE DUCT PENETRATION | | AT THIS LOCATION IN ACCORDANCE WITH FBC-M 607.5 AND | | FBC-M 607.8. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|