Plan Review Notes For Permit 09090594 |
Permit Number |
09090594 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-10-23 12:24:44 | *****DENIED***** | | | | 1. ON SHEET S-1, A PICTORIAL DEPICTING THE 15TH LEVEL | | PARTIAL FRAMING PLAN IS SHOWN. PLEASE EXPLAIN HOW THIS | | CORRESPONDS WITH 16TH FLOOR/SUITE 1600'S SCOPE OF WORK. | | | | 2. NO EXIT LIGHTS AND/OR EMERGENCY LIGHTS SHOWN FOR THE | | VACANT SPACE (1603). REFERENCE LS-1.0 AND E2.1 SHEETS. | | | | 3. ANY DOOR WHICH OPENS DIRECTLY INTO AN EXIT ACCESS | | CORRIDOR SHALL COMPLY WITH THE REQUIREMENTS IN | | ACCORDANCE WITH NFPA 80 AND SHALL BE WITH POSITIVE | | LATCH AND CLOSER. | | | | 4. SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES IN | | TERMS OF CLASS I OR CLASS II. | | | | 5. NO FIRE ALARM DEVICES SHOWN IN THE VACANT SPACE | | (1603) ON FA2.1 SHEET. | | | | 6. NO SPRINKLER HEADS SHOWN IN THE VACANT SPACE (1603) | | ON FS2.1 SHEET. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|