2009-10-11 12:37:09 | |
| |
| ** DENIED ** |
| |
| ** SUBMITTED FOR PERMIT APPLICATION BEFORE OCTOBER 1ST, |
| 2009 UNDER TBD ONLY. NO LICENSED CONTRACTOR HAS |
| APPLIED. |
| |
| |
| 1) NOTE: PLEASE SUBMIT MINIMUM PRESCRIPTIVE FOR COMMON |
| AREA CORRIDOR. IT IS NOT PERMITTED TO TRADE OFF TENANT |
| SPACE ALLOWANCES WITH THE TENANT SPACE. ONLY CORRIDORS |
| LOCATED IN THE TENANT SPACES ARE TRADABLE FOR OTHER |
| SPACES WITHIN TENANT. SEE 13-415.AB.5. THE PREVIOUS |
| TRADE OFF SECTION OF THE CODE WAS COMPLETELY REMOVED |
| WHICH STATED TRADE OFFS OF SPACES WERE OK AS LONG AS |
| THE TOTAL ALLOWANCE WAS NOT EXCEEDED. THIS OFFICE HAS |
| SPOKEN WITH THE STATE AS THE FLA COM PROGRAM WILL STILL |
| ALLOW IT. ALSO SPOKE TO THE STATE ABOUT COMMON AREAS |
| WHICH WOULD BE REQUIRED TO BE SEPARATED. THE CIRCUITS |
| FOR COMMON AREAS ARE SHOWN TO PANEL L413A WHICH PER |
| RISER IS A HOUSE PANEL. |
| **PLEASE NOTE BELOW FOR UPDATED HOUSE PANEL SCHEDULE |
| NEEDED. |
| SPACE 1687 IN THE IDR IS MISSING FIXTURE M4. 3-32W |
| |
| |
| 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULE FOR L413A |
| 408.4 |
| |
| 3) NOTE: POWER PLANS CONTAIN A NOTE #8 FOR RECEPTACLES |
| IN COMMON AREA WHICH STATES TO CIRCUIT TO LOCAL |
| CIRCUIT. THIS IS NOT ENOUGH INFORMATION. IT IS NOT |
| PERMISSIBLE TO CONNECT TO ANY EXISTING CIRCUIT IN THIS |
| AREA. |
| LOADS ON CIRCUITS, CIRCUITS FROM EMERGENCY SYSTEMS ARE |
| NOT PERMITTED TO FEED GENERAL PURPOSE RECEPTACLES. IF |
| THIS HAD BEEN THE ONLY COMMENT A PROVISO COULD BE GIVEN |
| TO FIND OUT CIRCUIT BEFORE INSPECTION AND TO SUBMIT |
| REVISED PLANS. HOUSE PANELS AND CIRCUITS IN THESE AREAS |
| SHOULD ALREADY PROVIDE AN ESTIMATED PANEL OR CIRCUIT. |
| 210.20,210.21,210.24, 408.4, 220.44 ETC |
| |
| 4) NOTE: PLEASE PLACE NOTE ON SHEETS E3.1 AND 3.2. NO |
| WIRING METHODS PERMITTED PER NEC 645 PERMITTED IN ROOMS |
| 1674, 1672. (OR WORDS TO THAT AFFECT). THESE ARE NOT IT |
| ROOMS, WALLS ARE NOT RATED, DOOR(S) ARE NOT RATED ETC. |
| WIRING METHODS PERMITTED IN NEC 645 ARE LESS STRINGENT |
| THAN WIRING METHODS OF OTHER CHAPTERS IN THE NEC. |
| PLEASE VERIFY WITH OWNER'S IT PERSONNEL THAT THESE |
| WIRING METHODS IN 645 ARE NOT GOING TO BE UTILIZED. |
| IF WIRING METHODS IN NEC 645 ARE DESIRED, THEN ALL OF |
| 645.4 1-5 MUST BE MET ALONG WITH NFPA-75 AS ADOPTED PER |
| FAC 69A-3.012. |
| |
| 5) NOTE: PLEASE COORDINATE PANELS AND RISER. BELOW ARE |
| SOME ITEMS WHICH DO NOT CORRELATE. |
| A) PLEASE SEE E 5.1 AS BOTH CIRCUITS LABELED TO L14D |
| AND SR14A ARE INDICATING CIRCUITING FROM A L13C PANEL. |
| HOWEVER THERE IS NO PANEL L13C ON RISER OR IN PANEL |
| SCHEDULES. (MISPRINT?) |
| |
| B) SEE RISER ON SAME SHEET AS THE CIRCUIT LABELED FROM |
| PANEL H14A FEEDING TRANSFORMER IS SHOWN TO A PANEL H13A |
| WHICH DOES NOT EXIST AS PART OF THIS PLAN. ( MISPRINT) |
| |
| C) SEE RISER ON THIS SAME SHEET WHICH INDICATES |
| T13A-1L, WHEN TRANSFORMER SCHEDULE IS T14A-1L. |
| (MISPRINT) |
| |
| D) SEE RISER TRANSFORMER IS LABELED AS T13A AND |
| TRANSFORMER LEGEND IS FOR T14A. (MISPRINT) |
| |
| RECEPTACLE LOCATED IN HALL IN THE NORTH AND WEST |
| CORRIDOR OF 1606 IS LABELED TO A CIRCUIT FOR NE |
| RECEPTACLES. THIS CAN BE ADJUST NOW OR FOR FINAL PLANS. |
| 408.4, FBC ADMIN 106.1.1,106.5 FOR CLARITY AND |
| COORDINATION OF RECORD PLANS. |
| |
| 6) NOTE: NO ACCESS CONTROL SYSTEM PART OF THE |
| ELECTRICAL REVIEW. PLANS MAY BE FOR ELECTRICAL J-BOX |
| LOCATIONS ONLY. SEPARATE PLANS AND PERMIT FOR ACCESS |
| CONTROL SYSTEM IS REQUIRED. NFPA-101 CHAPTER 7, 7.2 FOR |
| EGRESS CONTROLS. |
| |
| ** LOW VOLTAGE FOR DATA, PHONE ARE UNDER SEPARATE |
| PERMIT. MAY REFERENCE THESE PLANS FOR THESE SYSTEMS. |
| ** LOW VOLTAGE FOR FIRE ALARM SYSTEMS UNDER SEPARATE |
| PERMITS. BASE PLANS APPEAR TO SHOW COMPLIANCE WHICH IS |
| UNDER ELECTRICAL REVIEW FOR ADA AND BASE SYSTEM. REVIEW |
| BY FIRE MARSHALL IS STILL TO BE DONE. |
| |
| ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS |
| WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY |
| CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |