Plan Review Notes
Plan Review Notes For Permit 09090594
Permit Number 09090594
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-11 12:37:09 
  
 ** DENIED **
  
 ** SUBMITTED FOR PERMIT APPLICATION BEFORE OCTOBER 1ST,
 2009 UNDER TBD ONLY. NO LICENSED CONTRACTOR HAS
 APPLIED.
  
  
 1) NOTE: PLEASE SUBMIT MINIMUM PRESCRIPTIVE FOR COMMON
 AREA CORRIDOR. IT IS NOT PERMITTED TO TRADE OFF TENANT
 SPACE ALLOWANCES WITH THE TENANT SPACE. ONLY CORRIDORS
 LOCATED IN THE TENANT SPACES ARE TRADABLE FOR OTHER
 SPACES WITHIN TENANT. SEE 13-415.AB.5. THE PREVIOUS
 TRADE OFF SECTION OF THE CODE WAS COMPLETELY REMOVED
 WHICH STATED TRADE OFFS OF SPACES WERE OK AS LONG AS
 THE TOTAL ALLOWANCE WAS NOT EXCEEDED. THIS OFFICE HAS
 SPOKEN WITH THE STATE AS THE FLA COM PROGRAM WILL STILL
 ALLOW IT. ALSO SPOKE TO THE STATE ABOUT COMMON AREAS
 WHICH WOULD BE REQUIRED TO BE SEPARATED. THE CIRCUITS
 FOR COMMON AREAS ARE SHOWN TO PANEL L413A WHICH PER
 RISER IS A HOUSE PANEL.
 **PLEASE NOTE BELOW FOR UPDATED HOUSE PANEL SCHEDULE
 NEEDED.
 SPACE 1687 IN THE IDR IS MISSING FIXTURE M4. 3-32W
  
  
 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULE FOR L413A
 408.4
  
 3) NOTE: POWER PLANS CONTAIN A NOTE #8 FOR RECEPTACLES
 IN COMMON AREA WHICH STATES TO CIRCUIT TO LOCAL
 CIRCUIT. THIS IS NOT ENOUGH INFORMATION. IT IS NOT
 PERMISSIBLE TO CONNECT TO ANY EXISTING CIRCUIT IN THIS
 AREA.
 LOADS ON CIRCUITS, CIRCUITS FROM EMERGENCY SYSTEMS ARE
 NOT PERMITTED TO FEED GENERAL PURPOSE RECEPTACLES. IF
 THIS HAD BEEN THE ONLY COMMENT A PROVISO COULD BE GIVEN
 TO FIND OUT CIRCUIT BEFORE INSPECTION AND TO SUBMIT
 REVISED PLANS. HOUSE PANELS AND CIRCUITS IN THESE AREAS
 SHOULD ALREADY PROVIDE AN ESTIMATED PANEL OR CIRCUIT.
 210.20,210.21,210.24, 408.4, 220.44 ETC
  
 4) NOTE: PLEASE PLACE NOTE ON SHEETS E3.1 AND 3.2. NO
 WIRING METHODS PERMITTED PER NEC 645 PERMITTED IN ROOMS
 1674, 1672. (OR WORDS TO THAT AFFECT). THESE ARE NOT IT
 ROOMS, WALLS ARE NOT RATED, DOOR(S) ARE NOT RATED ETC.
 WIRING METHODS PERMITTED IN NEC 645 ARE LESS STRINGENT
 THAN WIRING METHODS OF OTHER CHAPTERS IN THE NEC.
 PLEASE VERIFY WITH OWNER'S IT PERSONNEL THAT THESE
 WIRING METHODS IN 645 ARE NOT GOING TO BE UTILIZED.
 IF WIRING METHODS IN NEC 645 ARE DESIRED, THEN ALL OF
 645.4 1-5 MUST BE MET ALONG WITH NFPA-75 AS ADOPTED PER
 FAC 69A-3.012.
  
 5) NOTE: PLEASE COORDINATE PANELS AND RISER. BELOW ARE
 SOME ITEMS WHICH DO NOT CORRELATE.
 A) PLEASE SEE E 5.1 AS BOTH CIRCUITS LABELED TO L14D
 AND SR14A ARE INDICATING CIRCUITING FROM A L13C PANEL.
 HOWEVER THERE IS NO PANEL L13C ON RISER OR IN PANEL
 SCHEDULES. (MISPRINT?)
  
 B) SEE RISER ON SAME SHEET AS THE CIRCUIT LABELED FROM
 PANEL H14A FEEDING TRANSFORMER IS SHOWN TO A PANEL H13A
 WHICH DOES NOT EXIST AS PART OF THIS PLAN. ( MISPRINT)
  
 C) SEE RISER ON THIS SAME SHEET WHICH INDICATES
 T13A-1L, WHEN TRANSFORMER SCHEDULE IS T14A-1L.
 (MISPRINT)
  
 D) SEE RISER TRANSFORMER IS LABELED AS T13A AND
 TRANSFORMER LEGEND IS FOR T14A. (MISPRINT)
  
 RECEPTACLE LOCATED IN HALL IN THE NORTH AND WEST
 CORRIDOR OF 1606 IS LABELED TO A CIRCUIT FOR NE
 RECEPTACLES. THIS CAN BE ADJUST NOW OR FOR FINAL PLANS.
 408.4, FBC ADMIN 106.1.1,106.5 FOR CLARITY AND
 COORDINATION OF RECORD PLANS.
  
 6) NOTE: NO ACCESS CONTROL SYSTEM PART OF THE
 ELECTRICAL REVIEW. PLANS MAY BE FOR ELECTRICAL J-BOX
 LOCATIONS ONLY. SEPARATE PLANS AND PERMIT FOR ACCESS
 CONTROL SYSTEM IS REQUIRED. NFPA-101 CHAPTER 7, 7.2 FOR
 EGRESS CONTROLS.
  
 ** LOW VOLTAGE FOR DATA, PHONE ARE UNDER SEPARATE
 PERMIT. MAY REFERENCE THESE PLANS FOR THESE SYSTEMS.
 ** LOW VOLTAGE FOR FIRE ALARM SYSTEMS UNDER SEPARATE
 PERMITS. BASE PLANS APPEAR TO SHOW COMPLIANCE WHICH IS
 UNDER ELECTRICAL REVIEW FOR ADA AND BASE SYSTEM. REVIEW
 BY FIRE MARSHALL IS STILL TO BE DONE.
  
 ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS
 WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY
 CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  