2009-09-25 19:20:22 | |
| |
| |
| ** DENIED PLANS ** |
| |
| **SUITE 1450 UNDER 09090526 |
| ** SUITE 1500 UNDER 09090527 |
| |
| ** TWO PERMIT APPLICATIONS SUBMITTED ALTHOUGH ONLY ONE |
| SET OF PLANS WERE SUBMITTED FOR BOTH FLOORS/SUITES. |
| |
| |
| 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS FOR ABOVE |
| SUITE ARE MISSING SOME SPACES/LIGHTING AND SOME |
| COORDINATION IS NEEDED FOR NUMBER OF FIXTURE, TYPES OF |
| FIXTURE/WATTAGE OF FIXTURES. |
| A) PLEASE SEE AREAS 1401,1411, 1400 ARE MISSING. |
| |
| B) PLEASE SEE AREA 1412 FOR EXAMPLE WHICH INDICATES |
| 5-32 WATT FIXTURES AND 2-56W FIXTURES. BASED ON THE |
| FIXTURE LEGEND THESE ARE NOT CORRECT. |
| BASED ON THE FIXTURE LEGEND THERE WOULD BE 2-32W, 3-56W |
| AND 1-14W. IT IS ACTUALLY LESS THAN SHOWN. HOWEVER |
| RECORD PLANS FOR THE NUMBER AND TYPE OF FIXTURES NEED |
| TO BE CORRECTED. |
| |
| C) PLEASE SPACE 1512 FOR EXAMPLE; CALCULATIONS STATE |
| 17-32 WATT FIXTURES. HOWEVER BASED ON THE PLANS AND |
| FIXTURE LEGEND THERE ARE MORE THAN ONE TYPE OF FIXTURE |
| IN THIS AREA. IN FACT THERE ARE THREE DIFFERENT TYPES |
| OF FIXTURES. SOME FIXTURES WITH LESS WATTAGE AND SOME |
| WITH MORE WATTAGE. SPECIFICALLY G FIXTURES WHICH ARE |
| NOT 32 WATT AS LISTED THEY ARE 50W. ALSO FIXTURE E |
| WHICH IS NOT 32 IT IS 13W. |
| |
| D) PLEASE SEE ROOM 1513 FOR EXAMPLE: CALCULATIONS |
| INDICATE 23-32W FIXTURES. HOWEVER BASED ON PLANS AND |
| FIXTURE LEGEND THERE ARE FIXTURES SUCH AS 4-G FIXTURES |
| WHICH ARE 50WATT FIXTURES. THE COUNT OF THE 32W F/F1 |
| FIXTURES IS 22. THE ACTUAL WATTAGE IN THIS ROOM IS |
| HIGHER. PLEASE ADJUST. |
| |
| *** KEEP IN MIND TRADE OFFS ARE ONLY PERMITTED WITHIN |
| THE TENANT SPACE. IT IS NOT PERMITTED TO TRADE COMMON |
| AREA HALLWAY AREAS WITH LIGHTING WITHIN THE TENANT |
| SPACE. |
| 13-415.AB.5, 13-415.B.1. SEE APPENDIX B |
| |
| 2) NOTE: PLEASE GO THROUGH PLANS AND COORDINATE ALL |
| CIRCUITING SO THAT LOADS SHOWN ON THE NUMBER OF |
| RECEPTACLES CAN BE REVIEWED FOR CODE COMPLIANCE. |
| |
| A) EXAMPLE: PLANS SHOW CIRCUIT JBL1-18 IN AREA 1533 AS |
| A DEDICATED RECEPTACLE HOWEVER PER THE SAME PANEL |
| SCHEDULE JBL1-18 STATES RECEPTACLES IN ROOM 1520. |
| ROOM 1520 INDICATES CIRCUIT AS JBL1-29 |
| |
| B) EXAMPLE: ROOM 1520 ABOVE NOTES JBL1-29 YET WHEN YOU |
| REVIEW THIS CIRCUIT ON PANEL SCHEDULE IT STATES ROOM |
| 1505, 1506. |
| |
| C) EXAMPLE: ROOM 1505 AS NOTED ABOVE IS THE WOMEN???S |
| BATHROOM HOWEVER BASED ON THE PLANS THERE IS NO |
| ELECTRICAL RECEPTACLES IN THIS AREA. ROOM 1505 IS |
| COMMON AREA WHY IS THIS BEING FED FROM TENANT |
| ELECTRICAL PANEL? |
| ROOM 1506 AS NOTED ON PANEL SCHEDULE IS ACTUALLY THE |
| WEST STAIRWAY AS SHOWN ON E2.2?? |
| |
| D) EXAMPLE: PANEL JBL1 IS A TENANT PANEL. PLEASE |
| EXPLAIN CIRCUITS 1,3,5,7,9 ETC WHICH ARE ALL SHOWN AS |
| CIRCUITS IN THE TENANT PANEL YET PER THE PLANS ALL THE |
| SPACES/ROOM LISTED ARE IN THE COMMON AREAS. |
| |
| E) EXAMPLE: PLEASE SEE PANEL L-14 CIRCUIT 11 WHICH IS |
| LISTED ON THE TENANT PANEL SCHEDULE FEEDING SPACE 1405, |
| HOWEVER SPACE 1405 ON THE PLANS IS ACTUALLY COMMON AREA |
| BATHROOM WHICH DOES NOT INDICATE ANY ELECTRICAL. |
| |
| F) EXAMPLE: L14-4 ON PLANS WHICH IS LOCATED IN ROOM |
| 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| |
| G) EXAMPLE: L14-6 ON PLANS WHICH IS LOCATED IN ROOM |
| 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| |
| H) EXAMPLE: L14-8 ON PLANS WHICH IS LOCATED IN ROOM |
| 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE. |
| |
| I) EXAMPLE: PLEASE SEE PANEL JBL2 CIRCUITS 19 AND 21. |
| BOTH OF THESE ARE INDICATING RECEPTACLES IN ROOM/AREA |
| 102, HOWEVER ROOM 1502 DOES NOT SHOW ANY ELECTRICAL |
| RECEPTACLES AS THIS IS THE VESTIBULE AREA. |
| |
| J) EXAMPLE: L14-7 SHOWN ON PLANS IN ROOM 1422 YET PANEL |
| SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA. |
| |
| K) EXAMPLE: L14-9 SHOWN ON PLANS IN ROOM 1422 YET PANEL |
| SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA. |
| |
| L) EXAMPLE: L14-12 SHOWN ON PLANS IN ROOM 1422 YET |
| PANEL SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON |
| AREA. |
| |
| ETC. |
| |
| |
| ****** IMPORTANT*** |
| THESE ARE ONLY SOME EXAMPLES OF CIRCUITING FOR 1450 AND |
| 1500 WHICH DO NOT COORDINATE. PLEASE GO THROUGH ALL |
| CIRCUITING AS THERE ARE NUMEROUS OTHERS. |
| LOADS ON CIRCUITS, LOADS ON PANELS AND LOADS ON SERVICE |
| CAN NOT BE VERIFIED. |
| SIZING OF OVER CURRENT PROTECTION FOR CIRCUITS ALSO CAN |
| NOT BE VERIFIED. |
| |
| ** TENANT SPACES SHALL BE CIRCUITED FROM THEIR PANELS |
| AND COMMON AREAS SHOULD BE CIRCUITED FROM HOUSE PANELS. |
| |
| 240.4,310.16.220.44,220.42, 240.24A, 240.24B ETC |
| |
| 3) NOTE: PLEASE EXPLAIN RISER. RISER INDICATES THE JBH |
| PANEL FED FROM GUTTER WITH TENANT METER HOWEVER THE |
| FEED TO TRANSFORMER WHICH FEEDS ALL TENANT PANELS JBL1, |
| 2 AND 3 YET THERE IS NOT METER ON RISER? |
| ALSO AS NOTED ABOVE FOR CIRCUITING CIRCUITS SUCH AS |
| H14-5 STATES CORRIDOR LIGHTING HOWEVER THIS IS |
| HOUSE/COMMON AREA? THERE ARE ALREADY HOUSE/COMMON AREA |
| PANELS SHOWN ON RISER. |
| AS NOTED ABOVE WITH THE CIRCUITING ETC NOT COORDINATED |
| FOR TENANTS AND COMMON AREAS, REVIEW AND CONFIRMATION |
| OF LOADS SHOWN ARE UNKNOWN FOR CODE COMPLIANCE. |
| |
| NEC 220,215, 210, 240, 310, ETC GIVEN AS GENERAL |
| CHAPTERS UNTIL PLANS ARE COMPLETE WITH ITEMS ABOVE. |
| |
| |
| |
| |
| |
| ** IMPORTANT** |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |