2009-10-08 19:42:52 | ** DENIED PLANS ** |
| |
| ** SOME OF THE ITEMS BELOW WOULD TYPICALLY BE REDLINED |
| HOWEVER THERE ARE SEVERAL OF THESE ITEMS WHICH COULD |
| NOT. |
| |
| 1) NOTE: PLANS INDICATE A RECEPTACLE FOR WATER HEATER |
| CONNECTION. PLEASE SEE 422.30, 422.31 FOR REQUIRED |
| DISCONNECT AND UNIT TO BE HARD-WIRED. |
| |
| 2) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION: |
| A) NO LOAD INFORMATION SHOWN FOR ELECTRICAL PANEL |
| SCHEDULE. NEC 220. PLEASE ALSO INCLUDE NEW LOADS AND |
| EXISTING SERVICE LOADS. |
| B) NO INFORMATION ON WHAT SIZE PANEL IS FEEDING LOADS. |
| C) NO INFORMATION FOR FEEDERS. 240.4, 310.15B6, 310.16, |
| 215.5 ETC |
| D) NO INFORMATION FOR MEANS OF DISCONNECT AT DETACHED |
| STRUCTURE PER 225.31-225.39 OR 230.70,71. |
| E) NO INFORMATION ON GROUNDING ELECTRODE SYSTEM AT THE |
| DETACHED BUILDING PER 250.32, 250.50 |
| |
| 3) NOTE: MISSING WALL RECEPTACLE PER 210.52 |
| |
| 4) NOTE: MISSING GARAGE RECEPTACLE PER 210.52G ALSO IS |
| REQUIRED TO BE GFI PER 210.8A2 |
| |
| 5) NOTE: *REDLINED SMOKE DETECTOR TO SMOKE ALARM. |
| NFPA-72 11.5.1, PLEASE ALSO SEE FLORIDA STATUES 553.885 |
| FOR REQUIRED CARBON MONOXIDE DETECTOR/ALARM. |
| |
| 6) NOTE: ARC FAULT PROTECTION PER 210.12 |
| |
| 7) NOTE: GFI IN BATHROOM PER 210.8A1. PLAN INDICATES |
| THE RECEPTACLE BUT NOT THE GFI. |
| |
| 8) NOTE: PANEL SCHEDULE INDICATES WALL MOUNTED A/C UNIT |
| HOWEVER PLANS DO NOT SHOW THE ELECTRICAL RECEPTACLE |
| LOCATION FOR UNIT. PLANS ONLY INDICATE THE GENERAL |
| PURPOSE RECEPTACLES. |
| |
| **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |