2009-10-08 19:42:52** DENIED PLANS **
  
 ** SOME OF THE ITEMS BELOW WOULD TYPICALLY BE REDLINED
 HOWEVER THERE ARE SEVERAL OF THESE ITEMS WHICH COULD
 NOT.
  
 1) NOTE: PLANS INDICATE A RECEPTACLE FOR WATER HEATER
 CONNECTION. PLEASE SEE 422.30, 422.31 FOR REQUIRED
 DISCONNECT AND UNIT TO BE HARD-WIRED.
  
 2) NOTE: PLEASE SUBMIT THE FOLLOWING INFORMATION:
 A) NO LOAD INFORMATION SHOWN FOR ELECTRICAL PANEL
 SCHEDULE. NEC 220. PLEASE ALSO INCLUDE NEW LOADS AND
 EXISTING SERVICE LOADS.
 B) NO INFORMATION ON WHAT SIZE PANEL IS FEEDING LOADS.
 C) NO INFORMATION FOR FEEDERS. 240.4, 310.15B6, 310.16,
 215.5 ETC
 D) NO INFORMATION FOR MEANS OF DISCONNECT AT DETACHED
 STRUCTURE PER 225.31-225.39 OR 230.70,71.
 E) NO INFORMATION ON GROUNDING ELECTRODE SYSTEM AT THE
 DETACHED BUILDING PER 250.32, 250.50
  
 3) NOTE: MISSING WALL RECEPTACLE PER 210.52
  
 4) NOTE: MISSING GARAGE RECEPTACLE PER 210.52G ALSO IS
 REQUIRED TO BE GFI PER 210.8A2
  
 5) NOTE: *REDLINED SMOKE DETECTOR TO SMOKE ALARM.
 NFPA-72 11.5.1, PLEASE ALSO SEE FLORIDA STATUES 553.885
 FOR REQUIRED CARBON MONOXIDE DETECTOR/ALARM.
  
 6) NOTE: ARC FAULT PROTECTION PER 210.12
  
 7) NOTE: GFI IN BATHROOM PER 210.8A1. PLAN INDICATES
 THE RECEPTACLE BUT NOT THE GFI.
  
 8) NOTE: PANEL SCHEDULE INDICATES WALL MOUNTED A/C UNIT
 HOWEVER PLANS DO NOT SHOW THE ELECTRICAL RECEPTACLE
 LOCATION FOR UNIT. PLANS ONLY INDICATE THE GENERAL
 PURPOSE RECEPTACLES.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  