Plan Review Notes
Plan Review Notes For Permit 09090432
Permit Number 09090432
Review Stop E
Sequence Number 2
Notes
Date Text
2009-10-26 08:36:46** PROVISO **
  
 ** REVISED PLANS TO BE SUBMITTED BEFORE ROUGH
 ELECTRICAL INSPECTION. ALL WIRING PER 2005 NEC, 2002
 NFPA-72.
  
 1) NOTE: PLEASE SUBMIT PANEL SCHEDULE (S) SHOWING ALL
 MINIMUM BRANCH CIRCUITS, OVER CURRENT PROTECTION SIZES
 AND CONDUCTOR SIZES. ALL CONDUCTOR SIZES AND BREAKERS
 CAN NOT BE VERIFIED AT THIS TIME. THIS WAS GONE OVER
 WITH ARCHITECT AS THERE IS UNCOVERED EXISTING
 ELECTRICAL NOT KNOWN AT THIS TIME.
 PLEASE SEE SECTIONS: 210.52, 210.52B1, 210.11C1, C2,
 C3, 210.52C1-C5, 210.8A6, 408.6, 310.16, 240.4 ETC
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  