Plan Review Notes For Permit 09090432 |
Permit Number |
09090432 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-09-23 14:54:55 | DENIED | | REFERENCE: | | FBC-2007 RESIDENTIAL | | | | 1. SHT A4.1 PLUMBING RISER DIAGRAM DOES NOT MEET CODE. | | PLEASE CORRECT THE FOLLOWING: | | A. MASTER BATH TUB VENT DOES NOT MEET THE REQUIREMENTS | | OF CODE SECTIONS P3104.3 & P3104.4. | | B. MASTER BATH W/C AND SHOWER SHALL CONNECT TO THE | | BRANCH LINE FOR THE BATHROOM FIXTURES, NOT THE W/M | | STACK. SECTION P3101.2. | | C. POWDER ROOM W/C SHALL CONNECT TO THE BRANCH LINE TO | | THE LAV, NOT THE STACK FOR THE SECOND FLOOR BATHROOM. | | SECTION P3107.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|