| ** DENIED PLANS ** |
| |
| * ELECTRICAL PERMIT IS BEING APPLIED FOR YET NO |
| ELECTRICAL PLANS/ DETAILS ARE BEING SUBMITTED. |
| |
| 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING SCOPE |
| OF WORK MEETING MINIMUM ELECTRICAL CODE COMPLIANCE WITH |
| THE 2005 NEC. ( NFPA-70). |
| PLANS INDICATE SOME NEW PARTITIONS ETC HOWEVER NO |
| ELECTRICAL IS SHOWN. |
| PLEASE SEE 210.52 FOR RECEPTACLE SPACE FOR WALLS. |
| PLEASE SEE 210.52B1 FOR MINIMUM SMALL APPLIANCE |
| CIRCUITS. |
| PLEASE SEE 210.52C1-5 FOR COUNTER SPACE RECEPTACLES |
| REQUIRED IN KITCHEN AND SEE 210.8A6 FOR GFI PROTECTION. |
| PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION. |
| PLEASE SEE 210.52D FOR REQUIRED BATHROOM RECEPTACLES. |
| PLEASE SEE 210.11C3 FOR THE BATH CIRCUITS. |
| PLEASE SEE 210.70 FOR LIGHTING AND CONTROL DEVICES. |
| ETC. |
| |
| 2) NOTE: PLEASE SEE R313.1.2 FOR SMOKE ALARMS WHICH ARE |
| REQUIRED TO MEET CURRENT NFPA-72 CODES. 11.5.1,11.8.3. |
| PLEASE SHOW LAYOUT OF EXISTING OR NEW MEETING CURRENT |
| CODES. |
| |
| ** IT IS IMPORTANT TO KNOW THAT AS NO ELECTRICAL IS |
| SHOWN OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE FOLLOWING REVIEW AS MINIMUMS CAN |
| NOT BE REVIEWED AT THIS TIME. |
| |
| **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |