2009-10-08 20:03:51 
 ** DENIED PLANS **
  
 * ELECTRICAL PERMIT IS BEING APPLIED FOR YET NO
 ELECTRICAL PLANS/ DETAILS ARE BEING SUBMITTED.
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING SCOPE
 OF WORK MEETING MINIMUM ELECTRICAL CODE COMPLIANCE WITH
 THE 2005 NEC. ( NFPA-70).
 PLANS INDICATE SOME NEW PARTITIONS ETC HOWEVER NO
 ELECTRICAL IS SHOWN.
 PLEASE SEE 210.52 FOR RECEPTACLE SPACE FOR WALLS.
 PLEASE SEE 210.52B1 FOR MINIMUM SMALL APPLIANCE
 CIRCUITS.
 PLEASE SEE 210.52C1-5 FOR COUNTER SPACE RECEPTACLES
 REQUIRED IN KITCHEN AND SEE 210.8A6 FOR GFI PROTECTION.
 PLEASE SEE 210.12 FOR REQUIRED ARC FAULT PROTECTION.
 PLEASE SEE 210.52D FOR REQUIRED BATHROOM RECEPTACLES.
 PLEASE SEE 210.11C3 FOR THE BATH CIRCUITS.
 PLEASE SEE 210.70 FOR LIGHTING AND CONTROL DEVICES.
 ETC.
  
 2) NOTE: PLEASE SEE R313.1.2 FOR SMOKE ALARMS WHICH ARE
 REQUIRED TO MEET CURRENT NFPA-72 CODES. 11.5.1,11.8.3.
 PLEASE SHOW LAYOUT OF EXISTING OR NEW MEETING CURRENT
 CODES.
  
 ** IT IS IMPORTANT TO KNOW THAT AS NO ELECTRICAL IS
 SHOWN OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW AS MINIMUMS CAN
 NOT BE REVIEWED AT THIS TIME.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  